To calculate the amperage at 220V AC for a 24kVA load, use the formula: Amps = kVA / Volts. Therefore, 24kVA / 220V = 109.09A. So, a 24kVA load at 220V AC would draw approximately 109.09 amps.
A 10kW heater at 220V would draw approximately 45.45 amps. This can be calculated using the formula: Amps = Watts / Volts. So, 10,000 Watts / 220 Volts = 45.45 amps.
The equation that you are looking for is I = E/R. Amps = Voltage/Resistance in ohms.
Each 32-watt bulb in a 48-inch fluorescent light typically draws around 0.27 amps. Therefore, a two-bulb setup would draw approximately 0.54 amps in total.
Depends on the size of the LED light and the voltage applied. An example is an LED 24 volt globe light that pulls 8 watts which draw 0.333333 amps. Take an LED 120 volt light bulb draws 12 watts and will pull 0.1 amps. The same bulb at 240 volts wil draw 0.05 amps. it really depends on the watts and voltage applied. An average would be about 0.1 amps.
To calculate the amperage at 220V AC for a 24kVA load, use the formula: Amps = kVA / Volts. Therefore, 24kVA / 220V = 109.09A. So, a 24kVA load at 220V AC would draw approximately 109.09 amps.
A 10kW heater at 220V would draw approximately 45.45 amps. This can be calculated using the formula: Amps = Watts / Volts. So, 10,000 Watts / 220 Volts = 45.45 amps.
It depends on the draw of the compressor.
About 0.6 amps for a 12v 21w bulb
The equation that you are looking for is I = E/R. Amps = Voltage/Resistance in ohms.
Each 32-watt bulb in a 48-inch fluorescent light typically draws around 0.27 amps. Therefore, a two-bulb setup would draw approximately 0.54 amps in total.
Depends on the size of the LED light and the voltage applied. An example is an LED 24 volt globe light that pulls 8 watts which draw 0.333333 amps. Take an LED 120 volt light bulb draws 12 watts and will pull 0.1 amps. The same bulb at 240 volts wil draw 0.05 amps. it really depends on the watts and voltage applied. An average would be about 0.1 amps.
1100 watts or about ten amps then another 3 to 4 amps for turn table light and fan
5500Watts/220V=25 Amps
Have to know the wattage or resistance of the lamp to answer this question.
Amp draw is always combined. 220V is uncertain if it is three phase or not, because there are both one phase and three phase applications of the 220V motor. In any case, the answer is always "combined".
To calculate the amperage for a 10kW heater on a 3-phase 220V system, use the formula: Amps = (kW x 1000) / (√3 x Volts). So, Amps = (10 x 1000) / (√3 x 220) = 26.18 amps per phase. Therefore, the total current drawn by the heater is 26.18 amps per phase multiplied by 3, which equals approximately 78.54 amps.