There should be a rating panel on the fan. Let's say it says 2A. You should not load the circuit any more than 80% of breaker rating. In our example 80% of 20 A is 16 A so you could handle 8 fans if they were 2 A each. However, the starting current of motors is higher than running current. Depending on speed setting of fans and if they are all started at the same time, the number may be less than 80% of load. Find the rating of your fans and do the calculations.
No, the six outlets are not amperage rated to be connected to a 20 amp circuit. A normal 15 amp receptacle can not be protected by a 20 amp breaker. Change the 20 amp breaker to a 15 amp breaker. This combination will pass code regulations. =============== In the United States, in a home, you can connect two hard-wired (not cord and plug connected) fans and six receptacles (outlets) to a single 20 amp circuit provided the 2 fans do not draw more than 10 amps together. If they are cord and plug connected, this limitation on the fans does not apply. In commercial and industrial installations, power to hard-wired equipment is provided on different circuits than receptacles.
Assuming each can light uses 1 amp, the ceiling fan uses 3 amps, and each outlet uses 2 amps, the total would be 13 amps. A 15-amp breaker would be sufficient for this setup with a little room for extra load.
A 15 amp breaker is not sufficient for a 225 amp load. You would need a breaker that matches the load current, such as a 225 amp breaker. Using a 15 amp breaker for a 225 amp load would cause the breaker to trip immediately due to overcurrent.
It's the amps that are controlled by the breaker not the volts. You can have a 600 volt 15 amp breaker, you can have a 347 volt 15 amp breaker. The breaker will trip when you exceed 15 AMPS.
No tandem breakers are of the same value.
Use 15 amp breaker with 14 gage wire or 20 amp breaker with 12 gage wire. Either way will work just fine.
No, the six outlets are not amperage rated to be connected to a 20 amp circuit. A normal 15 amp receptacle can not be protected by a 20 amp breaker. Change the 20 amp breaker to a 15 amp breaker. This combination will pass code regulations. =============== In the United States, in a home, you can connect two hard-wired (not cord and plug connected) fans and six receptacles (outlets) to a single 20 amp circuit provided the 2 fans do not draw more than 10 amps together. If they are cord and plug connected, this limitation on the fans does not apply. In commercial and industrial installations, power to hard-wired equipment is provided on different circuits than receptacles.
Assuming each can light uses 1 amp, the ceiling fan uses 3 amps, and each outlet uses 2 amps, the total would be 13 amps. A 15-amp breaker would be sufficient for this setup with a little room for extra load.
A 32 amp fixture can not be fed from a 20 amp breaker as the breaker will trip every time.
A 15 amp breaker is not sufficient for a 225 amp load. You would need a breaker that matches the load current, such as a 225 amp breaker. Using a 15 amp breaker for a 225 amp load would cause the breaker to trip immediately due to overcurrent.
Replace the 30 Amp Breaker with a 15 Amp breaker.
It's the amps that are controlled by the breaker not the volts. You can have a 600 volt 15 amp breaker, you can have a 347 volt 15 amp breaker. The breaker will trip when you exceed 15 AMPS.
A 50 amp breaker is an overcurent device.
No, you should not replace a 15 amp breaker with a 20 amp breaker without consulting a licensed electrician. The breaker size should match the wire size to prevent overheating and potential fire hazards.
You have a double pole breaker for 240Volt supply. The maximum current is 15 amp.
NO!
Yes, a 30 amp breaker is a 30 amp breaker. It must however be able to fit the box it is installed in.