There should be a rating panel on the fan. Let's say it says 2A. You should not load the circuit any more than 80% of breaker rating. In our example 80% of 20 A is 16 A so you could handle 8 fans if they were 2 A each. However, the starting current of motors is higher than running current. Depending on speed setting of fans and if they are all started at the same time, the number may be less than 80% of load. Find the rating of your fans and do the calculations.
A 15 amp breaker protecting # 14 wire.
No, the six outlets are not amperage rated to be connected to a 20 amp circuit. A normal 15 amp receptacle can not be protected by a 20 amp breaker. Change the 20 amp breaker to a 15 amp breaker. This combination will pass code regulations. =============== In the United States, in a home, you can connect two hard-wired (not cord and plug connected) fans and six receptacles (outlets) to a single 20 amp circuit provided the 2 fans do not draw more than 10 amps together. If they are cord and plug connected, this limitation on the fans does not apply. In commercial and industrial installations, power to hard-wired equipment is provided on different circuits than receptacles.
50 amp breaker.
It's the amps that are controlled by the breaker not the volts. You can have a 600 volt 15 amp breaker, you can have a 347 volt 15 amp breaker. The breaker will trip when you exceed 15 AMPS.
Depends on the size of the wire going to the A/C. If the wire is AWG #10 you cannot install a 40 amp breaker. If the wire is AWG #8 you can.
Use 15 amp breaker with 14 gage wire or 20 amp breaker with 12 gage wire. Either way will work just fine.
A 15 amp breaker protecting # 14 wire.
No, the six outlets are not amperage rated to be connected to a 20 amp circuit. A normal 15 amp receptacle can not be protected by a 20 amp breaker. Change the 20 amp breaker to a 15 amp breaker. This combination will pass code regulations. =============== In the United States, in a home, you can connect two hard-wired (not cord and plug connected) fans and six receptacles (outlets) to a single 20 amp circuit provided the 2 fans do not draw more than 10 amps together. If they are cord and plug connected, this limitation on the fans does not apply. In commercial and industrial installations, power to hard-wired equipment is provided on different circuits than receptacles.
50 amp breaker.
It's the amps that are controlled by the breaker not the volts. You can have a 600 volt 15 amp breaker, you can have a 347 volt 15 amp breaker. The breaker will trip when you exceed 15 AMPS.
A 32 amp fixture can not be fed from a 20 amp breaker as the breaker will trip every time.
Replace the 30 Amp Breaker with a 15 Amp breaker.
A 50 amp breaker is an overcurent device.
You have a double pole breaker for 240Volt supply. The maximum current is 15 amp.
NO!
Yes, a 30 amp breaker is a 30 amp breaker. It must however be able to fit the box it is installed in.
No more than 13 maximum on a 20 amp circuit.