15 amps at 120 volts will handle a maximum of 1800 watts. But you should never load the circuit to more than 80% which will be 1440 watts. Divide the wattage of each light into 1440 to see how many you can install. Example: Installing 75 watt fixtures you could install no more than 19. This is assuming there are only lights on the circuit and no outlets.
The number of can lights that can go on one breaker will depend on the wattage of each light and the maximum load capacity of the breaker. It's important to calculate the total wattage of all the lights and ensure it does not exceed the amp rating of the breaker to avoid overloading it. Consult with an electrician to determine the appropriate number of can lights that can safely go on one breaker.
You would need one 30 amp double-pole breaker in the breaker box for a 240V cooktop.
You can use a 15 amp single pole breaker to convert your 30 amp double pole breaker to 15 amp 120v. Simply replace the 30 amp breaker with the 15 amp breaker in the circuit breaker panel. Make sure to match the wire size in the circuit with the appropriate amperage rating of the new breaker.
No. The breaker must protect the circuit components such as wiring, outlets and switches that are connected to the breaker. Therefore if you have a 30 amp circuit as dictated by its components you need to protect it with a 30 amp or less breaker.
A 30 amp breaker is designed to trip at an earlier point than a larger 40 amp breaker so one appliance that operates on lower amperage level could be unsafe or damaged before it could trip the higher 40 amp breaker. Also, the existing wiring may not be rated for 40 amp service.
The number of can lights that can go on one breaker will depend on the wattage of each light and the maximum load capacity of the breaker. It's important to calculate the total wattage of all the lights and ensure it does not exceed the amp rating of the breaker to avoid overloading it. Consult with an electrician to determine the appropriate number of can lights that can safely go on one breaker.
A 30 amp breaker is usually used for a dedicated 30 amp device. Ordinary 15 amp receptacles can not be connected to a breaker of higher trip capacity than the rating of the receptacle. The wire size for a 30 amp breaker is #10 AWG.
You would need one 30 amp double-pole breaker in the breaker box for a 240V cooktop.
Household circuits come in two flavors, 15 amp and 20 amp. Check the circuit breaker or fuse in your panel to see which one your outlet is wired to. If the outlet is on a 15 amp circuit, you could only run one, but if you have a 20 amp circuit, you could get away with two, assuming there are no other appliances plugged into the same circuit. The electrical code says circuits should be loaded to no more than 80% of the breaker's rating. for a 20 amp breaker, that works out to 16 amps. Your two lamps would draw 16.6 amps, so you would be right at the limit.
Code only allows one wire to be connected to a single pole breaker. Any additional circuitry has to be done in a junction box downstream from the breaker.
Question makes no sense, but anyone would probably need to know the rating (watts) of the lights to give an answer.
You can use a 15 amp single pole breaker to convert your 30 amp double pole breaker to 15 amp 120v. Simply replace the 30 amp breaker with the 15 amp breaker in the circuit breaker panel. Make sure to match the wire size in the circuit with the appropriate amperage rating of the new breaker.
A tandem 20 amp breaker is designed to provide two separate circuits in one breaker slot, allowing for more circuits in a limited space. It is different from a standard single-pole breaker, which only provides one circuit per slot.
No. The breaker must protect the circuit components such as wiring, outlets and switches that are connected to the breaker. Therefore if you have a 30 amp circuit as dictated by its components you need to protect it with a 30 amp or less breaker.
A 30 amp breaker is designed to trip at an earlier point than a larger 40 amp breaker so one appliance that operates on lower amperage level could be unsafe or damaged before it could trip the higher 40 amp breaker. Also, the existing wiring may not be rated for 40 amp service.
NO! You are drastically in excess of electrical code requirement. A 15 amp circuit should not exceed eight total receptacles and/or lighting devices.
Multiple wires can be connected to one breaker but the one breaker IS a circuit. As long as the load is not more than 80% of the breaker capacity (example: a 20 amp breaker can only have 16 amps or 1920 watts at 120 volts) then by code as long as the load is not a specialty outlet of some sort, you can have as many outlets you want.