What size breakers are needed for a 30kva transformer 208 volt feed 600 volt out put
15 amps
An exact breaker size can not be given because the voltage, and hence the calculation for current, is not given. A transformer shall be protected by an over current device that is not rated at more that 150% of the primary current.
It depends on the current, not the power. There is insufficient information in the question to answer it. Please restate the question.
im have a 30 kva transformer 3 phase 480v 80 amp panel 120v what size disconnect should I use
P=1.73xVxIxCOSO KVA=KW/1.73xCOSO KVA=2000/1.4 KVA=1.42
9.5 Kva is the is the same as 9500 watts. Formula for Amps = Watts/Voltage. As you now can see you didn't give me any voltage so that the amperage can be calculated. Without the amps the wire size can not be calculated. Reply in a discussion if you are interested in an answer.
The question isn't the number of amps total on your branch circuits, but rather, what your MAIN breaker(s) are rated at. This will determine what size of generator you will need. And be certain that the generator is 3-phase. <<>> The formula you are looking for is Amps = kva x 1000/1.73 x voltage.
An exact breaker size can not be given because the voltage, and hence the calculation for current, is not given. A transformer shall be protected by an over current device that is not rated at more that 150% of the primary current.
A 15 KVA - Generator operating at 380 Volts can cater to only 22.79 Amps. It cannot cater to a 60 Amps breaker
if you have 200 kva so it's 160 KW then ,you need 400 A MCCB and setting at 0.9 and use cable 4c.185 mm2 if the SMDB is nearby and all this will be change according to the ambient temperature and the electrical code used in your area
It depends on the current, not the power. There is insufficient information in the question to answer it. Please restate the question.
You don't calculate the rated kV.A of a circuit breaker; it's determined by the manufacturer. It's important that a circuit breaker's rated kV.A exceeds the fault level kV.A at the point where the circuit breaker is located, otherwise it may fail to interrupt a fault current and, possibly, self destruct.
400amper Pumps are not rated in KW. I believe you mean kva, or, most likely in my mind, va. Please clarify what you have for a better answer. If you mean 132 kva, which to many people would mean the same thing as 132 KW, you are talking about a pump that is portable only because it is hauled around on a trailer. But that kind of pump wouldn't be submersible and would most likely not be electric. Motors are not often rated in va either, but if what you meant is 132 va, it will run on any common 15 or 20 amp circuit, assuming you connect it to the right voltage.
It depends totally on the voltage used.
16mm2
35 KVA generator using for load 100 meter length which cable need to used
How to compute for the size of wire in the primary side of 2500 kVA transformer 34.5kV
A 10 mm cable is most commonly used for a 500 KVA transformer, 240 volt, 3 phrase. The size of the wire that is used in a transformer is based on the voltage.