Best Answer

A 350 MCM copper conductor will limit the voltage drop to 3% or less when supplying 200 amps for 650 feet on a 240 volt system.

User Avatar

Wiki User

12y ago
This answer is:
User Avatar
More answers
User Avatar

AnswerBot

1w ago

For a 200 amp service running 650 feet, you would likely need at least 2/0 aluminum or 1/0 copper conductors for the hot lines. The size of the neutral conductor will depend on whether it is required to be the same size as the hot conductors or smaller, and the size of the ground conductor will need to follow local electrical code requirements. It is recommended to consult with a qualified electrician to ensure proper sizing for your specific application.

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What size conductors are needed to run a 650 foot residential underground electric service for a 200 amp service?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences

What is a service lateral conductor?

A service lateral conductor is a wire or cable that connects a building's electrical service panel to the electrical utility's distribution network. It carries electricity from the utility's distribution lines into the building to power electrical appliances and devices.


What are all of the conductors between the service equipment and the final branch circuit?

The conductors between the service equipment and the final branch circuit include service conductors, feeder conductors, and branch circuit conductors. Service conductors connect the utility service to the service equipment. Feeder conductors distribute power from the service equipment to the panelboard or distribution board. Branch circuit conductors then carry power from the panelboard to individual outlets, fixtures, and appliances.


What is the wire that runs from the electric meter to the breaker box called?

The wire that runs from the electric meter to the breaker box is called the service entrance cable or service wire. It is responsible for carrying the electricity from the meter into your home's electrical system through the breaker box.


Can the load wires in an electrical service panel exit from the same end as the service cable and meet code?

No, load wires in an electrical service panel should not exit from the same end as the service cable according to electrical codes. Load wires should enter the panel from the sides or bottom to prevent potential contact with live service conductors and ensure proper installation and safety.


For a 100 amp underground service to an unattached garage what size hot and neutral copper conductors do you need?

For a 100 amp underground service to an unattached garage, you would typically need to use 3 AWG copper conductors for the hot wires and 3 AWG copper conductors for the neutral wire. This size will ensure that the conductors can safely carry the required current without overheating. Additionally, you may need to refer to local electrical codes and regulations for specific requirements in your area.

Related questions

What size conductors are needed to run a 400 foot residential underground electric service?

Need to know what size service is going to be installed at the end of the run.


What is a service lateral conductor?

A service lateral conductor is a wire or cable that connects a building's electrical service panel to the electrical utility's distribution network. It carries electricity from the utility's distribution lines into the building to power electrical appliances and devices.


What is the cable between the service panel and electric meter called?

Whether you have an overhead or underground feed, that section of the installation is referred to as Service Entrance Conductors. On an overhead installation, it includes the conductors on BOTH sides of the meter, from the service drop conductors (attached at the service head) to the service equipment LINE terminals. On an underground installation, it refers only to the conductors between the meter's LOAD side and the service equipment LINE terminals. The conductors on the LINE side of the meter come from a distribution transformer and are unbroken between the transformer and your meter.


What are supply service conductors?

Supply service conductors are the electrical conductors that provide power from the utility company's distribution system to a building or structure. They carry electricity at a higher voltage level to supply the building's internal electrical system. These conductors are usually installed overhead on poles or underground in conduits.


What are all of the conductors between the service equipment and the final branch circuit?

The conductors between the service equipment and the final branch circuit include service conductors, feeder conductors, and branch circuit conductors. Service conductors connect the utility service to the service equipment. Feeder conductors distribute power from the service equipment to the panelboard or distribution board. Branch circuit conductors then carry power from the panelboard to individual outlets, fixtures, and appliances.


What is maximum amps for residential exterior light?

The maximum amps for residential exterior light have different steps. One is having the service equipment like the main panel, entrance conductors, and meter base also having guidelines and code summary.


What percentage of US has Residential Phone Service?

75% of US has Residential Phone Service.


What is the wire that runs from the electric meter to the breaker box called?

The wire that runs from the electric meter to the breaker box is called the service entrance cable or service wire. It is responsible for carrying the electricity from the meter into your home's electrical system through the breaker box.


Can the load wires in an electrical service panel exit from the same end as the service cable and meet code?

No, load wires in an electrical service panel should not exit from the same end as the service cable according to electrical codes. Load wires should enter the panel from the sides or bottom to prevent potential contact with live service conductors and ensure proper installation and safety.


Can triplex be run in underground conduit?

YesIn Canada the answer is no. Triplex is an aerial rated set of conductors that are used to bring the voltage from the utilities pole to the service drop at the home. Triplex consists of two ungrounded conductors wrapped around a neutral steel supported conductor. These conductors can be used on higher current capacities due to the direct cooling of the conductors by the surrounding air. This is why you will see a service drop of number 6 conductors supplying a 100 amp service. For a three phase four wire system quadplex is used to make three phase connections to commercial and industrial services.


What type of compression fittings can be used on an underground copper service pipe?

I am a Plumbing/HVAC Contractor and the type of fitting I always used for underground copper service pipe has been 3/4" (standard size for residential) brass flared fittings. A flared connection is a tight, secure connection guaranteed not to leak.


Where can I find good Residential Phone Service in Boston?

Verizon offers great Residential Phone Service in Boston