what kind of circuit? if it's a subfeed from one panel to another same size as hot wires. if it's a straight 240 volt circuit #8. depends on what kind of circuit.
AWG 2/0
Answer for USA, Canada and countries running a 60 Hz supply service.240 volt two wire circuits loads do not need a neutral to operate. A three wire 240 volt circuit that needs a neutral, will have a neutral the same size as the current carrying conductors. In this case a #10.
If you have 100 amp wire, you can use it for a 60 amp circuit, or for any circuit of 100 amps or less. But if you have a 60 amp circuit, 60 amp wire is thinner and cheaper than 100 amp wire.
120 amps The above answer is wrong. A 60 amp breaker is designed to trip at 60 amps be it a single pole, double pole or a triple pole that is used on three phase equipment. The number on the handle of a breaker is the trip capacity.
Answer for USA, Canada and countries running a 60 Hertz supply service.Yes, a 240v 50amp circuit can be changed to a 120v 30amp circuit. The wire for the 50 amp circuit should be a #6. This is more than ample for a 30 amp circuit. Remove the two pole 60 amp breaker and replace it with a single pole 30 and a single pole 15 amp breaker. One of the two #6 wires will be terminated on the neutral bus (if there is a white use it) and the other #6 will be terminated on the new 30 amp breaker. This will give you the required 120 volt 30 amp circuit. The new 15 amp breaker that was installed just to fill the hole from the two pole 60 amp breaker will give you a spare 15 amp circuit. I have no idea what you are trying to do, but there is no way you can change 220v 50 amp to 120v 30 amp. You can take 220 volt input in the top of your circuit breaker box. Then half of one side will be 120v and half of the other side will be 120v. You can install a 30 amp fuse. You should hire an electrician.Before you do any work yourself,on electrical circuits, equipment or appliances,always use a test meter to ensure the circuit is, in fact, de-energizedIF YOU ARE NOT REALLY SURE YOU CAN DO THIS JOBSAFELY AND COMPETENTLYREFER THIS WORK TO QUALIFIED PROFESSIONALS.
You need a 60 amp breaker.
Answer for USA, Canada and countries running a 60 Hz supply service.240 volt two wire circuits loads do not need a neutral to operate. A three wire 240 volt circuit that needs a neutral, will have a neutral the same size as the current carrying conductors. In this case a #10.
If you have 100 amp wire, you can use it for a 60 amp circuit, or for any circuit of 100 amps or less. But if you have a 60 amp circuit, 60 amp wire is thinner and cheaper than 100 amp wire.
On a fault condition of the circuit, the current most likely will not be removed. If this happens components in the circuit will most likely act as a fuse and will components will be completely destroyed. This is why the manufacturer recommends what size of fuse to use in their equipment and this fuse size should always be used.
AWG #6 wire.
The breaker protects the wiring not the boiler. 12,000 watts at 240 volts will require 50 amps. So, you will need a 60 amp breaker using AWG# 6 wire on a dedicated circuit.
no
120 amps The above answer is wrong. A 60 amp breaker is designed to trip at 60 amps be it a single pole, double pole or a triple pole that is used on three phase equipment. The number on the handle of a breaker is the trip capacity.
Answer for USA, Canada and countries running a 60 Hertz supply service.Yes, a 240v 50amp circuit can be changed to a 120v 30amp circuit. The wire for the 50 amp circuit should be a #6. This is more than ample for a 30 amp circuit. Remove the two pole 60 amp breaker and replace it with a single pole 30 and a single pole 15 amp breaker. One of the two #6 wires will be terminated on the neutral bus (if there is a white use it) and the other #6 will be terminated on the new 30 amp breaker. This will give you the required 120 volt 30 amp circuit. The new 15 amp breaker that was installed just to fill the hole from the two pole 60 amp breaker will give you a spare 15 amp circuit. I have no idea what you are trying to do, but there is no way you can change 220v 50 amp to 120v 30 amp. You can take 220 volt input in the top of your circuit breaker box. Then half of one side will be 120v and half of the other side will be 120v. You can install a 30 amp fuse. You should hire an electrician.Before you do any work yourself,on electrical circuits, equipment or appliances,always use a test meter to ensure the circuit is, in fact, de-energizedIF YOU ARE NOT REALLY SURE YOU CAN DO THIS JOBSAFELY AND COMPETENTLYREFER THIS WORK TO QUALIFIED PROFESSIONALS.
60 amp using AWG # 6 copper for branch circuits.
If youa are dealing with a 60 amp circuit you looking at a large system. If you have to ask this question you should notgo near it and you should contact an HVAC profesional. If youa are dealing with a 60 amp circuit you looking at a large system. If you have to ask this question you should notgo near it and you should contact an HVAC profesional.
You need a 60 amp breaker.
Typically, a 60 amp, 240 volt circuit. I hope that doesn't sound too sarcastic, but it's true. It's impossible to determine all of the devices that a person may need to operate on a 60 Amp circuit, but the simple reality is, if you don't need it, don't get it.