A # 10 wire with a insulation factor of 75 or 90 degrees C are both rated at 30 amps.
No, electrical code typically requires that circuits be protected by a breaker that matches the wire size. A 30 amp breaker is typically used for circuits with larger wire sizes. For a 120V circuit, a 20 amp breaker is more suitable with appropriate wire size.
No, you should match the breaker size to the wire gauge. A 10-2 wire is typically rated for a 30 amp breaker. Using a 20 amp breaker on 10-2 wire could result in overheating and a potential fire hazard.
Look on the heater and see what amps it is pulling. That will determine the wire size and breaker size. It must be on a dedicated circuit. 15 amps = AWG # 14 wire with 15 amp breaker 20 amps = AWG # 12 wire with 20 amp breaker 30 amps = AWG # 10 wire with 30 amp breaker 40 amps = AWG # 8 wire with 40 amp breaker
Depends on the wire size used in the circuit. If you use AWG # 14 wire you must use a 15 amp breaker. If it is wired with AWG # 12 wire then you use a 20 amp breaker. If a AWG # 10 wire is used then a 30 amp breaker is required. The breaker protects the wiring from overheating so you must use the proper size breaker for the wire used.
No, it is not safe to use 10 gauge wire with a 30 amp breaker as the wire is not rated for that high of a current. It is important to use the correct wire gauge that matches the breaker amperage to prevent overheating and potential fire hazards. For a 30 amp breaker, you should use at least 10 gauge wire.
The appropriate wire size for a 30 amp breaker is typically 10 gauge wire.
The recommended wire size for a 30 amp breaker is typically 10 gauge wire.
For a 30 amp breaker, you will need a wire that is at least 10 gauge in size.
Depends on the wire size you are using. If the generator breaker is a 30 amp then install a 30 amp breaker.
For a 30 amp breaker, a wire size of at least 10 gauge should be used to ensure safe and proper electrical connections.
30 amp breaker with #10 gauge copper wire
No, electrical code typically requires that circuits be protected by a breaker that matches the wire size. A 30 amp breaker is typically used for circuits with larger wire sizes. For a 120V circuit, a 20 amp breaker is more suitable with appropriate wire size.
No, you should match the breaker size to the wire gauge. A 10-2 wire is typically rated for a 30 amp breaker. Using a 20 amp breaker on 10-2 wire could result in overheating and a potential fire hazard.
Look on the heater and see what amps it is pulling. That will determine the wire size and breaker size. It must be on a dedicated circuit. 15 amps = AWG # 14 wire with 15 amp breaker 20 amps = AWG # 12 wire with 20 amp breaker 30 amps = AWG # 10 wire with 30 amp breaker 40 amps = AWG # 8 wire with 40 amp breaker
For a 30 amp breaker, a 10-gauge wire should be used.
Depends on the wire size used in the circuit. If you use AWG # 14 wire you must use a 15 amp breaker. If it is wired with AWG # 12 wire then you use a 20 amp breaker. If a AWG # 10 wire is used then a 30 amp breaker is required. The breaker protects the wiring from overheating so you must use the proper size breaker for the wire used.
Normally AWG #10 wire on a 30 amp breaker but it really depends on the size of the pump. The pump manufacture will specify the size wire and size breaker needed.