Q: What size wire for a 3 phase 50 amp compressor?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences
Related questions

What size wire for 240 volt 1 phase compressor?

If you have to ask here, you shouldn't be trying to wire in a 20A compressor. You will require a special circuit for the voltage and current with an independent breaker. Check your local code for the wire size or talk to a qualified electrician.


What wire size for 100 amp single phase 3 wire commercial service?

2 copper


What size wire to use with 50 amp 480v 3 phase so cord size?

6


What is the electrical rating for a Quincy QT-54-5-60VE air compressor?

Assuming your power supply is 230 volts, single phase: Full load amp draw = 21, circuit breaker = 50, minimum wire size = 10.


What is the amp size of a 8 wire?

The amp size of a wire is determined by its gauge, not the number of wires. An 8-gauge wire is typically rated for around 40-60 amps, depending on the type and insulation of the wire.


How do you wire an older 2 wire 30 amp compressor to a 3 wire 30 amp dryer plug?

If you have a 2-wire 30 amp compressor and you want to connect it to a 3-wire 30 amp dryer plug, you may need to install a new 3-wire power cord on the compressor that matches the dryer plug configuration. Make sure to follow the manufacturer's instructions and all safety guidelines when making any electrical connections.


What wire size required to carry single phase 100 Amp to the length of 2000 meter in India?

This is a voltage drop question. A voltage needs to be stated to answer this question.


What is amp size for 14 wire?

15 amps.


What size tech cable for 480 feet 100 amp?

This is a voltage drop to establish wire size question. For a correct answer to this question two values are needed. One value needed is the voltage and the other is whether it is three phase or a single phase installation.


What wire size to use for 90 amp load at 480V at 75 feet?

Up to about 100 ft the size of the wire is determined by the max current and not the distance. A 90 amp supply needs #6 wire. <<>> A #2 copper conductor will limit the voltage drop to 3 percent or less when supplying 90 amps for 75 feet on a three phase 480 volt system.


What size gauge wire for 4000w amp?

on a 4000 watt amp the best gauge wire woul be between 2 and 0


What size ground wire is needed for 20 amp?

For a 20 amp circuit, a 12-gauge copper ground wire is typically recommended. This wire size can safely handle the current and provide proper grounding for the circuit.