With very few exceptions your neutral and ground are always bonded together at the service. They can be bonded together anywhere from the transformer to the first overcurrent device, usually a panel, but in the transformer is where it is usually done.
Bonding the neutral keeps your voltages from floating. Without going into very technical explanation, suffice it to say that without proper bonding you can get different voltages supplied to various circuits in the building or home. Higher voltages can cause burn out of fixtures or equipment and lower voltages can burn up motors or keep lights from providing adequate light.
No, in a sub-panel of an outbuilding, the neutral and ground should be kept separate and not bonded together. This is to prevent the potential for ground loops and to ensure proper functioning of the grounding system.
Some electric panels have the ground and neutral bonded together for safety reasons. This bonding can help prevent dangerous voltage levels and reduce the risk of electrical shocks in case of a fault. However, it is important to check local electrical codes and guidelines before making any modifications to ensure compliance and safety.
Ground wire can be appropriately bonded to the neutral and cabinet at the service box by connecting the neutral and ground wires from the feeder wires to the neutral bus bar and the ground terminal located on the same cabinet at the service box. White wire (neutral) must be connected to bus bar and bare wire must be connected to ground terminal in the same cabinet.
If you are reading a voltage it is the drop across the resistance to ground. To get rid of the voltage get the resistance lower. This can be accomplished by installing more ground rods to the grounding system. Utility companies usually like 3 ohms to ground or less.
If you are measuring 115VAC on the neutral bus in a panel with a separate ground bus, it could indicate a few potential issues. One common reason is that there is a loose or disconnected neutral wire somewhere in the circuit. This could result in the neutral not being properly connected back to the transformer, leading to a voltage differential between the neutral and ground buses. It's important to investigate and address this issue promptly to prevent potential electrical hazards.
The secondary side (output) of a three phase transformer develops a "separately derived system". That is why you do notsupply a neutral to a three phase transformer. It develops its own reference to ground by being bonded to the transformer casing and to a substantial earth ground, such as a ground rod. The XO tap on a transformer provides the neutral to the secondary line. It will have a double wire lug. The neutral wire going to the panel being supplied goes under one lug and the same size wire is to go to the ground lug on the transformer chassis The ground lug is also a double with the other lug to be wired to the earth ground.
The neutral of a transformer is usually grounded. Under this situation, this question is the same as asking whether you can apply a voltage to ground; the answer is yes, but I don't know why you'd want to. Sometimes transformer neutrals are insulated away from ground. If this is done, then you could inject "backwards" from the neutral up into the transformer. Again, I don't know why you would want to do this, though.
No, in a sub-panel of an outbuilding, the neutral and ground should be kept separate and not bonded together. This is to prevent the potential for ground loops and to ensure proper functioning of the grounding system.
Answer for USA, Canada and countries running a 60 Hertz supply service.Nothing but the neutral bus should be bonded to the ground electrode.
Some electric panels have the ground and neutral bonded together for safety reasons. This bonding can help prevent dangerous voltage levels and reduce the risk of electrical shocks in case of a fault. However, it is important to check local electrical codes and guidelines before making any modifications to ensure compliance and safety.
fff
The rounded third prong goes to earth ground at the main panel where the neutral is also bonded to ground.
Ground wire can be appropriately bonded to the neutral and cabinet at the service box by connecting the neutral and ground wires from the feeder wires to the neutral bus bar and the ground terminal located on the same cabinet at the service box. White wire (neutral) must be connected to bus bar and bare wire must be connected to ground terminal in the same cabinet.
If you are reading a voltage it is the drop across the resistance to ground. To get rid of the voltage get the resistance lower. This can be accomplished by installing more ground rods to the grounding system. Utility companies usually like 3 ohms to ground or less.
An earthing transformer provides a neutral in a delta connected system.
A current transformer is primarily used at the neutral point of a transformer for earth fault protection. A neutral current transformer will measure any ground fault current which will essentially flow from the star point of the transformer. A fault-detection device other devices is connected to the current transformer and, if the fault current exceeds a certain trigger value, the fault-detection device will give a trip command to an earth-fault relay to disconnect the supply of electricity to the transformer.
If you are measuring 115VAC on the neutral bus in a panel with a separate ground bus, it could indicate a few potential issues. One common reason is that there is a loose or disconnected neutral wire somewhere in the circuit. This could result in the neutral not being properly connected back to the transformer, leading to a voltage differential between the neutral and ground buses. It's important to investigate and address this issue promptly to prevent potential electrical hazards.