The resistance for 400 ft. of 10 AWG copper is .4 ohms. This would be a voltage drop of (.4 x 20) or 8 volts. For 120 VAC service this is a 6% which is a bit high. At 240 volts it is 3%. At 8 AWG the resistance is .251 ohms which will give you better performance.
A 3/0 copper or 4/0 aluminum wire is typically used for a 200 amp residential service panel. It's important to consult the National Electrical Code (NEC) and local building codes to ensure compliance and safety. It's also recommended to consult with a licensed electrician for guidance on specific wiring requirements for your installation.
Assuming you are working with 240v, you need 4/0 copper conductors.
For a 400 amp service, you would typically use 500 kcmil copper wire or 600 kcmil aluminum wire for the main service conductors. It's important to consult with a licensed electrician and check local electrical codes to ensure the correct wire size is used for your specific installation.
The wire size used in a service entrance distribution panel is governed by the size of the services over current device. The larger the service, the larger the fault current could be, the larger the ground wire to carry the fault current to ground. If the largest service conductor carries 100 amps use a #8, 200 amps - #6, 400 amps - #3, 600 amps - #1, 800 amps - 1/0 and over 800 amps - 2/0 for the ground wire. <<>> Golden Valley Electric Assoc. in Alaska requires #4AWG copper wire for a ground from the breaker box to earth ground rod. The same goes from the service entrance panel on the pole.
For 2000 amps, you would typically use a wire size of 400 MCM (thousand circular mils) or larger to safely carry that level of current. It is important to consult local electrical codes and a professional electrician to determine the exact wire size needed for your specific application.
Use AWG # 4 copper and you will have a 2.6% voltage drop which is acceptible.
A #4 copper conductor will limit the voltage drop to 3% or less when supplying 25 amps for 400 feet on a 120 volt system.
500mcm 37 strand copper wire = 1.544lbs/ft.
A 228 sq mm conductor equates to 450 MCM. A conductor of 450 MCM is not a standard AWG wire size. A standard 400 MCM will carry 380 amps. A standard 500 MCM will carry 430 amps. Difference between 400 and 500 MCM amperage's is 50 amps. Transposing between the two amperage's of 50 amps will be 380 + 25 = 405 or 430 - 25 = 405 amps. This is a very rough calculated answer for the question.
A 3/0 copper or 4/0 aluminum wire is typically used for a 200 amp residential service panel. It's important to consult the National Electrical Code (NEC) and local building codes to ensure compliance and safety. It's also recommended to consult with a licensed electrician for guidance on specific wiring requirements for your installation.
Assuming you are working with 240v, you need 4/0 copper conductors.
400 MCM (thousand circular mils) copper wire weighs approximately 1.51 pounds per foot.
For a 400 amp service, you would typically use 500 kcmil copper wire or 600 kcmil aluminum wire for the main service conductors. It's important to consult with a licensed electrician and check local electrical codes to ensure the correct wire size is used for your specific installation.
The wire size used in a service entrance distribution panel is governed by the size of the services over current device. The larger the service, the larger the fault current could be, the larger the ground wire to carry the fault current to ground. If the largest service conductor carries 100 amps use a #8, 200 amps - #6, 400 amps - #3, 600 amps - #1, 800 amps - 1/0 and over 800 amps - 2/0 for the ground wire. <<>> Golden Valley Electric Assoc. in Alaska requires #4AWG copper wire for a ground from the breaker box to earth ground rod. The same goes from the service entrance panel on the pole.
A 600 MCM copper conductor with an insulation factor of 75 or 90 degree C is rated at 420 and 455 amps respectively. This is very large diameter wire to handle. The best way of wiring this service is to use parallel runs. A 3/0 copper conductor with an insulation factor of 75 or 90 degrees C is rated at 200 and 210 amps respectively. So depending on the insulation of the wire that is used, a parallel wire configuration will give you a total of 400 at 75 degrees C or 420 at 90 degrees C.
Depends upon the voltage. The formula for amperage or (wire size) is Watts / Voltage. If the voltage is 220 volts, then the amperage would be over 400 amps. This would require a large wire size to run it. If it were 440 volts, the amperage would be 1/2 or 200 amps. That would require a smaller wire size. As the voltage goes up, the amperage goes down. At a thousand volts, the amperage would only be 90 amps. A wire gauge or size of a #2 would carry 90 amps for small distances.
For a distribution panel rated at 400 amps parallel runs of 3/0 conductors will do the job.