answersLogoWhite

0


Best Answer

The key is that you don't want to cause over-heating in wire. The answer is you can probably do what you want unless it involves high current and a small cross section in wire mold such that the Romex could generate too much heat. You could always strip out the wires inside the Romex and just run them in the wire mold.

User Avatar

Wiki User

14y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Can you run Romex through a wire mold?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Electrical Engineering

Can 2 lengths of 14 Ga romex be used to make a 30 A circuit?

No, electrical wires can only be run in parallel on wire sizes 1/0 and larger. To supply a load of 30 amps you will need #10 wire and a 30 amp breaker.


Does 6 gauge wire need to be in a conduit if run in a finished garage along the wall and ceiling?

If you are talking about #6 building wire, it needs to have mechanical protection. This means that it has to be run in conduit. If you are talking about #6 cable set like Romex, then it only has to have mechanically protection below a five foot elevation from the garage's finished floor. If the wall that the cable set is running in is going to be finished with drywall or plywood then that is considered protected.


When is it permissible to wire tie a wire to a conduit?

What kind of wire? If it's a power wire, why is the place wired with conduit? Commercial buildings must put all power wiring in conduit, so if you're planning to run romex in a commercial building, the answer would be "no", it's not permissible. If it's data wire, note that there may be some "crossover" interference if the data wire follows a power wire for very much distance. It's usually not a problem to cross a conduit and tie to it, but it's generally recommended that you not tie data cable to conduit.


How to run a cable underfloor from a wall socket?

Yes, as long as you do not run it under the floor joists. New electrical code requires that you drill a hole through the floor joists and run the wire through those holes. It cannot be hanging under the floor joists. If you see wires are already running under the floor joists then go ahead and run the wire under the joists attaching it on every other joists with a wire staple. Make sure they wire does not make contact with any metal ductwork or any other metal objects. Match the wire with what is already in the wall outlet you are jumping off of. If it is 12/2 then use 12/2, if it is 14/2 then use 14/2. Never mix wire gauges.


Can you run thhn conductors exposed?

n you run thhn wire in a cable tray

Related questions

Is that possible to run romex wire to the under ground basement?

If the wire is to be buried you'll need to use "direct burial" wire; if you're staying inside the house, just under the floor and above the concrete or dirt, standard romex should be fine.


My breaker says use 75 degree wire can i use 90?

You can use 90 degree celcius rated wire. It just must be derated to the 75 degree column in the book NFPA 70 article 310.16 table. Meaning, if you are running romex wire, you don't have to run larger wire in most situations.


Can 2 lengths of 14 Ga romex be used to make a 30 A circuit?

No, electrical wires can only be run in parallel on wire sizes 1/0 and larger. To supply a load of 30 amps you will need #10 wire and a 30 amp breaker.


How many watts can run through wire?

1,200


Can you use single conductor 14 gauge wire to wire a three way switch?

The key is the protection of the wires. If you are using single wires you will need a conduit of some sort. Don't just run the single wires in the wall. Multi wire Romex or metallic shielded cable are used to provided added protection to the encased conductors.


Is it possible to remove mold from a children's bike trailer made of canvas?

Remove the cover and run it through the wash.


What was the Berlin Wall before it was a wall?

It was a barrier of barbed wire. When people began to run through the wire, they built it into a wall.


Is electricity faster in a thick or thin wire?

They run through both evenly! .o.


Does 6 gauge wire need to be in a conduit if run in a finished garage along the wall and ceiling?

If you are talking about #6 building wire, it needs to have mechanical protection. This means that it has to be run in conduit. If you are talking about #6 cable set like Romex, then it only has to have mechanically protection below a five foot elevation from the garage's finished floor. If the wall that the cable set is running in is going to be finished with drywall or plywood then that is considered protected.


When is it permissible to wire tie a wire to a conduit?

What kind of wire? If it's a power wire, why is the place wired with conduit? Commercial buildings must put all power wiring in conduit, so if you're planning to run romex in a commercial building, the answer would be "no", it's not permissible. If it's data wire, note that there may be some "crossover" interference if the data wire follows a power wire for very much distance. It's usually not a problem to cross a conduit and tie to it, but it's generally recommended that you not tie data cable to conduit.


Is electricity faster in a thick wire or thin one?

They run through both evenly! .o.


How can a coil of wire pick up a nail?

When a wire has an electric current run through it it produces a magnetic feild. A coil of wire (also called a selonoid) produces a strong magnetic feild perpindicular to the turns of wire when a current is run through it. This is also known as electric magnet. Its also worthy to note that speakers work based off of this concept