The key is that you don't want to cause over-heating in wire. The answer is you can probably do what you want unless it involves high current and a small cross section in wire mold such that the Romex could generate too much heat. You could always strip out the wires inside the Romex and just run them in the wire mold.
No, electrical wires can only be run in parallel on wire sizes 1/0 and larger. To supply a load of 30 amps you will need #10 wire and a 30 amp breaker.
If you are talking about #6 building wire, it needs to have mechanical protection. This means that it has to be run in conduit. If you are talking about #6 cable set like Romex, then it only has to have mechanically protection below a five foot elevation from the garage's finished floor. If the wall that the cable set is running in is going to be finished with drywall or plywood then that is considered protected.
What kind of wire? If it's a power wire, why is the place wired with conduit? Commercial buildings must put all power wiring in conduit, so if you're planning to run romex in a commercial building, the answer would be "no", it's not permissible. If it's data wire, note that there may be some "crossover" interference if the data wire follows a power wire for very much distance. It's usually not a problem to cross a conduit and tie to it, but it's generally recommended that you not tie data cable to conduit.
Yes, as long as you do not run it under the floor joists. New electrical code requires that you drill a hole through the floor joists and run the wire through those holes. It cannot be hanging under the floor joists. If you see wires are already running under the floor joists then go ahead and run the wire under the joists attaching it on every other joists with a wire staple. Make sure they wire does not make contact with any metal ductwork or any other metal objects. Match the wire with what is already in the wall outlet you are jumping off of. If it is 12/2 then use 12/2, if it is 14/2 then use 14/2. Never mix wire gauges.
n you run thhn wire in a cable tray
No, it is not possible to run Romex wire directly underground in a basement. Romex wire is not rated for direct burial underground and should not be used in this application. Instead, you should use UF-B (underground feeder) cable or conduit with appropriate wiring for underground installations.
No, electrical wires can only be run in parallel on wire sizes 1/0 and larger. To supply a load of 30 amps you will need #10 wire and a 30 amp breaker.
1,200
THHN is a single-conductor wire typically used in conduit for indoor wiring, while Romex is a brand of non-metallic sheathed cable that contains multiple insulated conductors in a flexible plastic jacket. THHN must be used inside conduit, while Romex can be run along surfaces or in walls without conduit.
No, Romex cable is not allowed to be run inside conduit. Romex cable is intended to be used in exposed or concealed applications within buildings. If conduit is used, it should contain individual THHN/THWN wires instead of Romex cable.
Remove the cover and run it through the wash.
It was a barrier of barbed wire. When people began to run through the wire, they built it into a wall.
To run a power wire through the firewall on a 2002 Saturn L200, locate an existing grommet or firewall penetration point that is not in use. Ensure it is a safe and secure passage point before passing the wire through. Be sure to seal the opening properly after routing the wire to prevent water or debris from entering the cabin.
Running electricity through a coil of wire will create a magnetic field around the wire. This phenomenon is known as electromagnetism. The strength of the magnetic field can be increased by increasing the current flowing through the wire or by adding more coils to the coil.
They run through both evenly! .o.
If you are talking about #6 building wire, it needs to have mechanical protection. This means that it has to be run in conduit. If you are talking about #6 cable set like Romex, then it only has to have mechanically protection below a five foot elevation from the garage's finished floor. If the wall that the cable set is running in is going to be finished with drywall or plywood then that is considered protected.
What kind of wire? If it's a power wire, why is the place wired with conduit? Commercial buildings must put all power wiring in conduit, so if you're planning to run romex in a commercial building, the answer would be "no", it's not permissible. If it's data wire, note that there may be some "crossover" interference if the data wire follows a power wire for very much distance. It's usually not a problem to cross a conduit and tie to it, but it's generally recommended that you not tie data cable to conduit.