You can use the wire rated for 20 amps on a 15 amp receptacle but you can not use a 20 amp fuse on any device rated at 15 amps.

This is a tricky part of the code about receptacle outlets, You can use a 15 amp duplex outlet on a 20 amp circuit. (duplex outlet two devices can plug in) If it is a single outlet then the outlet must be rated 20 amp. NEC table210.21(B)(3).

============

A 15 amp duplex receptacle can be wired to a 20 amp rated circuit. This means the breaker OR fuse protecting the circuit can be rated 20 amps if the wire is also rated at 20 amps (12 AWG). --Sparkfighter

User Avatar

Wiki User

12y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Can you use a 20 amp fuse and wire rated for it in a 15 amp outlet?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences

What size of wire use if you have 6 outlet with 30 amp breaker?

It is unusual to have multiple outlets on a 30 Amp service. If you do this you need outlets rated at 30 amps and 10 AWG wire.


How do you change from 15 amp fuse to 20 amp fuse?

The only way you can change a 15 amp to a 20 is you have to replace the 14 gauge wire going to it with a 12 gauge wire, then replace the 15 amp breaker with a 20 amp breaker. You can put a 15 amp outlet on a 20 amp circuit as long as there is more then one receptacle. A double receptacle counts as two receptacles. Steve Green Coeur d'Alene, Idaho


Can 10-2 wire be used for an outlet?

Yes you can. The existing 30 amp breaker on the two conductor #10 wire will have to be changed out to a two pole 20 amp breaker. The reason for this change out is that the new 20 amp outlet is only rated at 20 amps maximum. If the 30 amp breaker were left feeding the 20 amp device, It would be unsafe as it is 10 amps higher that the manufacturer's specifications of maximum amperage handling capacity of a 20 amp device.If the 30 amp circuit is only 120 volts, the neutral will have to be lifted from the neutral bar of that circuit and that will be the second wire that will be connected to the new two pole 20 amp breaker. This action will give you 240 volts across the new 20 amp outlet.


Can a 10 amp AGC fuse be used in a 10 amp rated DC circuit?

Yes, as long as the fuse is able to be inserted into the fuse holder it will work.


What amp fuse do you use for a 100 watt bulb?

Fuses or breakers are used to protect the conductor to the load. A #14 wire conductor is rated for 15 amps. Most home circuitry is done with #14 wire. The minimum size breaker in an electrical panel is 15 amp so it looks like a 15 amp fuse or breaker can be used for a 100 watt light bulb.

Related questions

What size of wire use if you have 6 outlet with 30 amp breaker?

It is unusual to have multiple outlets on a 30 Amp service. If you do this you need outlets rated at 30 amps and 10 AWG wire.


What does the 20 amp power outlet fuse do on a 1999 Dodge Durango?

What does the 20 amp power outlet fuse do on a 1999 dodge durango


Can a 15 amp breaker that supplys an outlet be replaced it with a 30 amp without starting a possible fire?

Not without moving up two wire sizes from a #14 copper wire rated for 15 amps to a #10 copper wire rated for 30 amps.


Can you replace a 30 amp fuse with a 15 amp fuse?

Not a good idea. The 15 amp fuse will be protection a #14 wire which is rated for 15 amps maximum capacity. By changing the 15 amp fuse to a 30 amp fuse you would then be allowing 30 amps maximum capacity on a #14 wire. By doubling the load the extra heat generated on the smaller wire could be enough to melt the insulation from the wire and that could cause the wire to short out. If the wire shorts out inside the wall it means the removal of the wall board to replace the wire to restore the circuit to an operational condition. The proper wire sizing for a 30 amp fuse is, #10 copper wire with an insulation rating of 90 degrees C.


How many watts is a 240 volt 20 amp fuse rated for with 12 gauge wire?

4800


If your fuse box supports 20 amp fuses can you replace one current 15 amp fuse with a 20 amp fuse?

The purpose of a fuse it to protect the wire that goes to the load. A 15 amp fuse protects a #14 gauge wire. A 20 amp fuse protects a #12 gauge wire. To answer your question if the wire size is #12 coming from the 15 amp fuse now then it can be upped to 20 amp fuse. If it isn't then you are taking the risk of overloading the #14 wire with a 20 amp fuse. This can lead to insulation failure of the #14 wire, overheating with the possible outcome of a fire breaking out somewhere in the circuit.


Can 50 Amp breaker replace 45 Amp breaker?

Both a 45 amp and 50 amp breaker would require 6 AWG wire. So if you have 6 AWG wire and any devices like an outlet are rated at 50 amps or greater you are okay.


What is thicker a 8amp fuse wire or a 15amp wire?

The 15 amp fuse.


Can you replace a 15 amp fuse with a 30 amp fuse?

Not a good idea. The 15 amp fuse will be protection a #14 wire which is rated for 15 amps maximum capacity. By changing the 15 amp fuse to a 30 amp fuse you would then be allowing 30 amps maximum capacity on a #14 wire. By doubling the load the extra heat generated on the smaller wire could be enough to melt the insulation from the wire and that could cause the wire to short out. If the wire shorts out inside the wall it means the removal of the wall board to replace the wire to restore the circuit to an operational condition. The proper wire sizing for a 30 amp fuse is, #10 copper wire with an insulation rating of 90 degrees C.


How do you choose the right fuse for the job?

The correct size fuse needed is based on the size wire used in the circuit. The size wire needed is based on the load that will be applied to the circuit. 1. AWG 14/2 wire = 15 amp fuse 2. AWG 12/2 wire = 20 amp fuse 3. AWG 10/2 wire = 30 amp fuse 4. AWG 8/2 wire = 40 amp fuse


Can 600v wire works 30 amp fuse?

What size is the wire? AWG 10, 600V is rated for 30 amps. Any AWG less than 6 would also be ok for a 30 amp circuit....


How do you change from 15 amp fuse to 20 amp fuse?

The only way you can change a 15 amp to a 20 is you have to replace the 14 gauge wire going to it with a 12 gauge wire, then replace the 15 amp breaker with a 20 amp breaker. You can put a 15 amp outlet on a 20 amp circuit as long as there is more then one receptacle. A double receptacle counts as two receptacles. Steve Green Coeur d'Alene, Idaho