Check the MFG for the amps it uses, if it is suppose to be on a regular 20amp line,
then replace the breaker with a 20amp breaker. With the 30amp breaker,it will work,
but if there is a surge, you could send too much power to the appliance and fry it.
Most refrigerators, are just on a regular 120v household outlet. Besides a 30amp
breaker must have 10ga wire, if the wire is 12ga,it can not be attached to a 30amp breaker.
No, they each need their own breaker of the right amp. Neither of them would cause the breaker to trip if there was a problem.
50 amp breaker.
Yes, as long as the rating of the breaker is high enough. Do not use a 20 amp breaker with 14 ga wire however. 14 ga wire can not have a breaker ratered high than 15 amps serving it.
Depends on the size of the wire going to the A/C. If the wire is AWG #10 you cannot install a 40 amp breaker. If the wire is AWG #8 you can.
No tandem breakers are of the same value.
Not unless the wire going to the refrigerator outlet is AWG 10/2. If it is wired with 12/2 wire then you must use a 20 amp breaker. Using a 30 amp breaker is dangerous and a fire hazard.
For a standard size refrigerator, a dedicated 15 amp circuit is used.
No, they each need their own breaker of the right amp. Neither of them would cause the breaker to trip if there was a problem.
50 amp breaker.
Yes, as long as the rating of the breaker is high enough. Do not use a 20 amp breaker with 14 ga wire however. 14 ga wire can not have a breaker ratered high than 15 amps serving it.
Replace the 30 Amp Breaker with a 15 Amp breaker.
A 50 amp breaker is an overcurent device.
You have a double pole breaker for 240Volt supply. The maximum current is 15 amp.
NO!
Yes, a 30 amp breaker is a 30 amp breaker. It must however be able to fit the box it is installed in.
Resistance is Volts over Current 11 Ohm = 110Volt / 10 Amp
Depends on the size of the wire going to the A/C. If the wire is AWG #10 you cannot install a 40 amp breaker. If the wire is AWG #8 you can.