Depends on how far you want to carry that load.

For short distances, 6 AWG THHN rated at 90C, used at 30C ambient, is permitted for up to 75 Amps when in a 3-conductor cable or conduit.

In free air, it may be "capable" of handling up to 105 amps.

NEC Table 310.16 and 310.17.

User Avatar

Wiki User

11y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: How many amps will thhn 6 wire carry?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

How many amps will 200ft of 6ga wire carry?

50 amps.


How many amps will 4.0 gauge wire carry?

140 AMPS


How many amps will a 4 gauge aluminum wire carry?

70 amps.


How many amps can 4 ought aluminum wire carry?

Aluminum 4/0 wire car carry 180 amps at at 75 degrees Fahrenheit or 205 amps at 90 degrees. .


How many amps will a 2 0 wire carry?

If you mean 2/0 copper wire it is rated 175 amps. # 2 wire is 115 amps. If you are referring to 2.0 metric it is rated 15 amps.


How many amps can 16 gauge wire carry at 120 vac at 25 feet?

18 amps.


How many amps can 14awg 105 degree C carry?

A wire with the stats 14awg and 105 degrees Celsius can carry up to 39 amps.


How many automotive amps can 30 foot strand of copper wire carry?

Need to know the wire size.


What is the maximum amps for 12 gauge wire?

It depends more on the insulation type not the voltage A very common wire type is THHN According to NEC (electrical standard popular in the USA) this type wire in size #12 is rated for 30 amps, but there is a footnote that states it can only be used for 20 amps maximum


How many amps will 10-2 wire carry at 40 feett?

30 amps is how much a 10-2 wire will carry at 110 feet. 10 gauge wire is only good for thirty amps per the national electrical code. Using 80% of the breakers usage you will actually be getting only 24 amps.


Will awg 10 wire carry 30 amps for 30feet?

Yes, a #10 wire will carry 30 amps for 30 feet. If the load is rated as continuous then the wire will have to be derated to 80% capacity which will leave you with 24 workable amps. If the load demands currents higher that 24 amps then you will have to go to the next wire size up which is a #8 which is rated at 45 amps.


Can you run thhn conductors exposed?

n you run thhn wire in a cable tray