Depends on the wattage. For example a 60W incandescent bulb draws about 1/2 amp so you could have thirty. Since you typically de-rate to 80% of the value of the breaker it would be 24.
It's the amps that are controlled by the breaker not the volts. You can have a 600 volt 15 amp breaker, you can have a 347 volt 15 amp breaker. The breaker will trip when you exceed 15 AMPS.
try higher amp breaker
No. The 20 amp breaker is probably protecting a #12 wire. Connecting a 40 amp breaker to the 20 amp #12 wire would seriously overload the #12 wire. This means that if the load increased to a full 40 amps the insulation on the smaller size wire would most likely melt off and the wire could short out.
It is a relay or switch problem. A circuit breaker or fuse won't keep a light on.
Yes, considering you can do that on 15 amp breaker easy.Experience in construction field. The worst that will happen is that the breaker will trip off after a few minutes.In the formula W = A x V. W = 20 x 120 = 2400 watts. If you want you can operate two 1000 watt lamps from a 20 amp breaker operating on 120 volts.
It's the amps that are controlled by the breaker not the volts. You can have a 600 volt 15 amp breaker, you can have a 347 volt 15 amp breaker. The breaker will trip when you exceed 15 AMPS.
try higher amp breaker
Rule of thumb would be 8.
I really need more detailed information to answer your question. How many lights were added and what wattage bulbs are being used? For a 15-amp breaker, the maximum wattage it would handle would be around 1650 watts. This would be about 16 100-watt bulbs. Does your breaker trip immediately when you turn the light switch on? If you have an ohmmeter you can check the tripped breaker. Put one lead on the black "hot" wire coming from the breaker. Remember, the breaker must be off. Then put the other lead on the ground bar. If the ohm reading is very low, close to 2 ohms, then you have a direct short to ground somewhere in your wiring.
No. The 20 amp breaker is probably protecting a #12 wire. Connecting a 40 amp breaker to the 20 amp #12 wire would seriously overload the #12 wire. This means that if the load increased to a full 40 amps the insulation on the smaller size wire would most likely melt off and the wire could short out.
Anything that does not pull over 50 amps.
Use AWG 12/2 with ground.
Not if it's functioning properly. The purpose of a circuit breaker is to shut off power if the circuit exceeds the rated power capacity of the wires. Don't plan to exceed the 30 Amp capacity of your house wiring; the results will be destructive.
It is a relay or switch problem. A circuit breaker or fuse won't keep a light on.
Yes, considering you can do that on 15 amp breaker easy.Experience in construction field. The worst that will happen is that the breaker will trip off after a few minutes.In the formula W = A x V. W = 20 x 120 = 2400 watts. If you want you can operate two 1000 watt lamps from a 20 amp breaker operating on 120 volts.
Ground wire connects to the ground bar, white wire connects to the neutral bar, and black wire connects to the breaker. Be sure and turn off main breaker before installing the wire or the breaker.
There are two things to think about here. First of all a 200 amp breaker will not physically fit into a 100 amp panel. This is so designed because the panel buss is not designed to conduct 200 amps before the current is cut off. A 100 amp rating on the panel is the maximum amount of current that the manufacturer states, that can be handled safely. Second if the 200 amp breaker is in the main panel then everything downstream from that breaker has to be rated for 200 amp conductivity. The wire size will have to be 3/0 from the breaker to the first over current device in the sub panel which will be the sub panel's main breaker. The sub panel can not be a load center but will have to be a combination panel. I doubt that the 100 amp sub panel's main breaker lugs would be large enough to connect the 3/0 cable.