Q: If you're installing a circuit that will contain receptacles in an industrial area and the first receptacle is more than 50 feet (15.24 meters) from the load center you should?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

Why would receptacles have low voltage and the light switches no voltage on the same circuit?

lighting is usually on 15A breakers receptacles on 20A the probability is high that they are not on the same circuit. if they are the same circuit the probability is high that there hasn't been an electrical inspection


What is downstream in electrical?

The terminology down stream refers to an electrical circuit and where devices are connected into the circuit. In reference to the breaker that feeds the circuit everything is down stream from it. If a GFCI receptacle is added into the circuit as the first device, the GFCI can be wired to allow all of the regular receptacles to be protected down stream from that GFCI. Every device added to the circuit will be down stream from the one that is ahead of it. The only device that will not have something down stream from it will be the last device in the circuit.


No power in three wall receptacles. Replaced circuit breaker. Still no power. How to fix?

With electricity, once you have tried the circuit breakers, it is safest to get a qualified electrician to fix the problem......electricity is dangerous if you do not know what you are doing.


Can you replace an ungrounded circuit breaker with a GFCI circuit breaker?

Yes but it's redundant and may cause unnecessary "tripping" of the circuit. The GFCI circuit breaker is intended to protect an entire receptacle circuit whereas a GFCI receptacle is designed to protect only that receptacle and any which are provided power from its load side. (downstream)


How many 120VAC single-phase output receptacles does a 25kW Power Distribution panel have?

If you are referring to the 25KW Power Distribution Panel used by the military, NSN: 6110-01-244-3209, there are four 120VAC, 20A circuit breakers and four corresponding twist lock receptacles.

Related questions

Can you control 10 outlets with one 20 amp GFCI outlet on one 20 amp circuit?

Yes. I know of no limits to how many regular receptacles (outlets) you can "piggy back" onto one GFCI receptacle. However, in commercial and industrial construction there are limits to how many receptacles can be placed on any one circuit. These limits in the United States and according to the NEC are: 10 receptacles on a 15 amp circuit and 13 receptacles on a 20 amp circuit.


Where must GFCI receptacles be installed in residential garages?

All receptacles in a garage must be GFCI protected by code. Typically, the first receptacle in the circuit (location is irrelevant) must be a GFCI, then all others down stream in the circuit will be protected, and can be common receptacles.


Does the NEC code allow multiple 20A receptacles on a 20A circuit Put another way does a 20A receptacle with T shaped neutral slots imply that no other outlets are that circuit?

The National Electrical Code (US) allows up to thirteen 20 amp receptacles on a 20 amp circuit. 120V x 20A = 2400 VA each duplex receptacle is calculated at 180 VA 2400 / 180 = 13.3333 receptacles, since you can't put a third of a receptacle in, you have to round down to 13.


Can a 20 amp circuit breaker operate two 15 amp receptacle?

It is perfectly acceptable to have (2) 120 volt 15 amp receptacles operated from a 120 volt 20 amp circuit breaker (as a general rule of thumb 11 receptacles are acceptable on a 20 amp circuit). The 15 amp rating of the receptacle is the maximum allowed amperage that should be hooked up to the receptacle at any one time. So in this case the limiting factor is the amount of current being drawn across both receptacles simultaneously should not exceed the 20 amp rating of the circuit breaker. In the United States the NEC code allows the use of a 20 amp circuit breaker to feed a branch circuit consisting of 15 amp receptacles. Generally you would not exceed 11 receptacles though as you will assume an average load of 1.5 amps per receptacle and trying to maintain about 80% max load.


Can duplex oulet have one dedicated outlet?

Answer for USA, Canada and countries running a 60 Hertz supply service.Yes, if it is connected with a three wire circuit such as kitchen counter receptacles. In this case both top and bottom of the duplex receptacle are dedicated circuits. An example of a duplex receptacle being the only device in the circuit from a 15 amp breaker is the receptacle for a microwave oven.


How is a plug in receptacle connected to other receptacles in a normal house circuit?

There are typically 8 to 10 receptacles on most house circuits with special applications in Kitchens. The wires are in parallel with Black to Black, White to White and Bare Wire Ground to Ground.


What is the formula to figure out how many plugs and lights you can put on a circuit?

This depends upon the circuit breaker capacity. You may never load a circuit to greater than 80% of it's capacity. So you may load up to 12 Amps on a 15 Amp circuit, and, 16 Amps on a 20 Amp circuit. The National Electrical Code requires you to calculate each receptacle at 180 VA. If the circuit is 120 volts and 15 amps, you would have 1800 VA, divide by 180 VA per receptacle, equals 10 receptacles per circuit (minus the wattage of each luminaire or light fixture added to the circuit, before dividing by the 180 VA). If the circuit is 120 volts and 20 amps, you would have 2400 VA, divide by 180 VA per receptacle, equals 13.333 receptacles per circuit (round down to 13 receptacles),(minus the wattage of each luminaire or light fixture added to the circuit, before dividing by the 180 VA).


How many electrical receptacles on 15 A breaker with 12 gauge wire?

In the United States and according to the NEC, in commercial and industrial installations, you are limited to 10 receptacles on a 15 amp circuit. The size of the wire is not a determining factor. There is no limit to the number of receptacles on a circuit in a home and there may be local codes where you live that have stricter requirements.


When installing an isolated circuit in a patient care area what color conductor is required to be terminated on the nickel-plated screw of a receptacle?

When installing and Isolated circuit, the orange-insulated conductor is required to be connected to the nickel-plated screw of recepticals


Why would someone use two positive wires to complete a house 2 plug receptacle circuit?

If the 2 hot wires are connected to either side of a receptacle, you have a 240v receptacle (assuming it's in the US). This is typically done for window air conditioners. But code requires that the receptacle have a different configuration than other receptacles in the building so you don't run the risk of plugging in a 120v device into a 240v receptacle.


Why does my GFI circuit trip every few weeks even with nothing is plugged and the outlet was already replaced?

Receptacles are daisy chained so that one receptacle also powers others. A GFCI is often in the first receptacle so that a fault on any other connection/receptacle will be detected and cut off by that GFCI. Trip the GFCI. Then find all receptacles and appliances now without power. A fault can be in any one or due to a combination of many slightly defective appliances.


DoesCode permit connecting receptacles to a 20ampere branch circuit using short lengths of 14AWG conductors as the pigtail between the receptacle terminals and the 12AWG branch-circuit conductors?

No. This practice is a violation of Article 210.19 (A) of the NEC. "Conductors of branch circuits supplying more than one receptacle for cord-and-plug-connected portable loads shall have an ampacity of not less than the rating of the branch circuit."