Code test question.
30 amps maximum.
The grounding conductor of a service distribution is sized by the ampacity of the service. By just stating the wire size, this does not give this information, as many variables enter into what wires are used depending on length, ambient temperature and insulation factor to name a few.
The ampacity for copper is 1000A per square inch, in some places is 700A psi.
Conductors by code are only allowed to be loaded up to 80 percent. In this case an over size wire set will be higher that what the wire is rated for in the code book. A 600 MCM copper conductor with an insulation factor of 90 degrees C is rated at 455 amps. Paralleled together will give an ampacity of 910 amps. After the derate the maximum amperage allowed is 728 amps. So to get the full 900 amp the wire size has to be increased to a 1000 MCM copper conductor with an insulation factor of 90 degrees C which is rated at 585 amps. Paralleled this give you an ampacity of 1170 amps. After the derate the maximum amperage allowed is 1170 x 80% = 936 amps
A 10 mm squared conductor is equal to a #8 AWG. A #8 copper conductor with an insulation factor of 75 or 90 degrees C are both rated at 45 amps.
It will taken 8 amps <<>> The conversion of 2.5 sq mm wire to AWG is equal to a #12 wire. The ampacity of a #12 copper wire with an insulation factor of 90 degrees C is 20 amps.
A #8 copper wire with an insulation factor of 75 or 90 degrees C has an ampacity of 45 amps. A #8 wire with an insulation factor of 60 degrees C has an ampacity of 40 amps.
The grounding conductor of a service distribution is sized by the ampacity of the service. By just stating the wire size, this does not give this information, as many variables enter into what wires are used depending on length, ambient temperature and insulation factor to name a few.
The ampacity for copper is 1000A per square inch, in some places is 700A psi.
Conductors by code are only allowed to be loaded up to 80 percent. In this case an over size wire set will be higher that what the wire is rated for in the code book. A 600 MCM copper conductor with an insulation factor of 90 degrees C is rated at 455 amps. Paralleled together will give an ampacity of 910 amps. After the derate the maximum amperage allowed is 728 amps. So to get the full 900 amp the wire size has to be increased to a 1000 MCM copper conductor with an insulation factor of 90 degrees C which is rated at 585 amps. Paralleled this give you an ampacity of 1170 amps. After the derate the maximum amperage allowed is 1170 x 80% = 936 amps
Allowable ampacity for 10-2 copper NM-B is 30 A.http://www.cerrowire.com/default.aspx?id=46
Copper Loss at 75 C = Copper Loss at Ambient Temperature C * (310/(235+Ambient Temperature C))
A 10 mm squared conductor is equal to a #8 AWG. A #8 copper conductor with an insulation factor of 75 or 90 degrees C are both rated at 45 amps.
The wire ampacity of #12 copper wire with an insulation factor of 90 degrees C is 20 amps. If the load is of a continuous nature e.g. baseboard heaters then the wire has to be de-rated to 18 amps
It will taken 8 amps <<>> The conversion of 2.5 sq mm wire to AWG is equal to a #12 wire. The ampacity of a #12 copper wire with an insulation factor of 90 degrees C is 20 amps.
Isn't it 35, according to the NEC 310.15(B)(16) Table.
Copper wires do not hold amps, they have a cross sectional area capacity to allow amperage to flow. In the electrical trade this is spoken of as "ampacity" of the wire. It is a combining of the two words amps and capacity. A # 2 copper wire with an insulation factor of 60, 75 or 90 degrees C is consecutively rated at 100, 115 and 120 amps.
copper