answersLogoWhite

0


Best Answer

The grounding conductor of a service distribution is sized by the ampacity of the service. By just stating the wire size, this does not give this information, as many variables enter into what wires are used depending on length, ambient temperature and insulation factor to name a few.

User Avatar

Wiki User

11y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What size copper grounding electrode conductor is required for a service that has three sets of 600 kc mil copper conductors per phase?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Electrical Engineering

Does the grounding bar hook to meterbox or breaker box?

A grounding bar is most often located in the breaker panel. This is where all your grounding conductors are landed. If the panel is your primary service panel, neutrals and grounds can both be landed there. The NEC (US) requires that all service equipment be bonded together. This includes your meterbox. To most people bonding and grounding look alike but they serve different purposes. In most cases this bonding consists of a #6 AWG solid copper conductor connecting your service panel to your meterbox and also whatever you happen to be using as a grounding electrode, usually a water pipe and ground rod. Consult a competent electrician for what is required in your area. I was on a job once where the city inspector expected this bonding conductor to be run with the service conductors inside the same conduit, which is what I would expect. But the power company for the same job required it to be run outside the conduit which is acceptable practice. Both were right, but we had to do it one way for the inspection and another way before power was supplied.


What earth size is required for 16mm live and neutral?

Answer for USA, Canada and countries running a 60 Hz supply service.Equipment grounding conductors are not based on the size of the live and neutral conductors. Equipment grounding conductors are based on the amp rating of the circuit, which may or may not be the same ampacity of the conductors of the circuit.However, working backwards, a 16mm conductor is the same as a 3/0 conductor, which is rated for 200amps, which requires an equipment grounding conductor (earth) of at least 6 AWG copper / 4 AWG aluminum. If your circuit is rated higher (usually the breaker size) than 200 amps a larger conductor may be required.As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.Before you do any work yourself,on electrical circuits, equipment or appliances,always use a test meter to ensure the circuit is, in fact, de-energized.IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOBSAFELY AND COMPETENTLYREFER THIS WORK TO QUALIFIED PROFESSIONALS.


What size grounding conductor is needed for a 80 amp service?

For service sizes of 100 amps and less a #8 bare copper conductor is required.


What is a grounded conductor used for and what color is it required to be by NFPA 70 the national electric code?

A grounding conductor is a means for providing safety for users of electrical devices that may have experienced an internal failure that causes an electrical short to metallic surfaces. In theory, such a short to a GROUNDED surface would quickly result in overcurrent or ground-fault interruption of the circuit, resulting in an dead but safe circuit. NEVER "reset" a GFCI while holding the attached device or without discovering what caused it to trip. Were it not for a grounding conductor, the user could become the "grounding conductor" by accident, causing electrocution. Grounding conductors maybe bare (copper) wires or have green insulation, or green with a yellow stripe (also used for bonding) or other green markings (green screws, green clips, green wire nuts, etc). Grounded appliance plugs were not required in the NEC until the 1960s.


What size and type of wire is used for ground in 200 amp service?

Minimum size grounding conductor for a 200 amp service entrance is #6 bare copper. The conductor connected to a metal water pipe, or whatever your primary grounding electrode is, is required to be #4 copper. This size requirement is often missed. The conductor connected to a ground rod is only required to be #6 regardless of the size of service. Typical installation is #6 bare solid copper.

Related questions

If you have a 400 Amp service using 500 MCM What size grounding electrode conductor is required?

#2


What is the difference between a ground conductor and a ground electrode conductor?

# A ground electrode conductor is a conductor that originates at the neutral or equipment ground buses in the main service entrance panel board or separating derived system (e.g. isolation transformer) # A ground electrode is a item that is in contact with the earth (e.g. Building metal frame, underground continuous metallic water pipe etc...) # A ground conductor is a conductor that is used to keep an electrical system continuous. Ground conductors are required, by code, in all PVC conduit runs. Ground conductors are also used to keep all metallic components of the installation at the same zero potential to overcome mechanical connections that would not carry a fault current back to the supply distribution panel.


How many ground rods are required for a 200amp service in Indianapolis?

According to the NEC, if the ground rod supplements another grounding electrode such as a metal water pipe, you are required 1. If the ground rod or rods is your only grounding electrode, you are required at least 2, at least 6 feet apart. Check with your local jurisdiction for local requirements.


Does the grounding bar hook to meterbox or breaker box?

A grounding bar is most often located in the breaker panel. This is where all your grounding conductors are landed. If the panel is your primary service panel, neutrals and grounds can both be landed there. The NEC (US) requires that all service equipment be bonded together. This includes your meterbox. To most people bonding and grounding look alike but they serve different purposes. In most cases this bonding consists of a #6 AWG solid copper conductor connecting your service panel to your meterbox and also whatever you happen to be using as a grounding electrode, usually a water pipe and ground rod. Consult a competent electrician for what is required in your area. I was on a job once where the city inspector expected this bonding conductor to be run with the service conductors inside the same conduit, which is what I would expect. But the power company for the same job required it to be run outside the conduit which is acceptable practice. Both were right, but we had to do it one way for the inspection and another way before power was supplied.


What earth size is required for 16mm live and neutral?

Answer for USA, Canada and countries running a 60 Hz supply service.Equipment grounding conductors are not based on the size of the live and neutral conductors. Equipment grounding conductors are based on the amp rating of the circuit, which may or may not be the same ampacity of the conductors of the circuit.However, working backwards, a 16mm conductor is the same as a 3/0 conductor, which is rated for 200amps, which requires an equipment grounding conductor (earth) of at least 6 AWG copper / 4 AWG aluminum. If your circuit is rated higher (usually the breaker size) than 200 amps a larger conductor may be required.As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.Before you do any work yourself,on electrical circuits, equipment or appliances,always use a test meter to ensure the circuit is, in fact, de-energized.IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOBSAFELY AND COMPETENTLYREFER THIS WORK TO QUALIFIED PROFESSIONALS.


What size grounding conductor is needed for a 80 amp service?

For service sizes of 100 amps and less a #8 bare copper conductor is required.


What is a grounded conductor used for and what color is it required to be by NFPA 70 the national electric code?

A grounding conductor is a means for providing safety for users of electrical devices that may have experienced an internal failure that causes an electrical short to metallic surfaces. In theory, such a short to a GROUNDED surface would quickly result in overcurrent or ground-fault interruption of the circuit, resulting in an dead but safe circuit. NEVER "reset" a GFCI while holding the attached device or without discovering what caused it to trip. Were it not for a grounding conductor, the user could become the "grounding conductor" by accident, causing electrocution. Grounding conductors maybe bare (copper) wires or have green insulation, or green with a yellow stripe (also used for bonding) or other green markings (green screws, green clips, green wire nuts, etc). Grounded appliance plugs were not required in the NEC until the 1960s.


What is the minnimum size equipment grounding conductor required by the NEC for a branch-circuit protected by a 50-ampere rated circuit breaker?

#10 copper


How do you find a good online tranlater?

Grounding Electrodes and Grounding Electrode Systems All grounding electrodes present at a building or structure must be bonded together to form a grounding electrode system, as required by NEC® Section 250.50. Doing so eliminates voltage gradients, and also improves reliability and grounding performance over time by creating redundancy. If one electrode is damaged, destroyed by corrosion, or removed, other electrodes are available to maintain the all-important connection from the service equipment to ground. Section 250.53(B) states that two or more grounding electrodes effectively bonded together are considered a single grounding electrode system. Permitted Electrodes The NEC recognizes the following seven types of grounding electrodes [250.52(A)]: Metal underground water pipe Metal frame of a building or structure Concrete-encased electrodes Ground ring Rod and pipe electrodes Plate electrodes Other local metal underground systems or structures (piping, tanks, well casings, etc.)


Classification, basic concepts and installation of grounding devices?

Grounding device is also called grounding integration device: a device that forms an electrical connection between electrical equipment or other objects and the ground. (Building Electrical Construction Technology). The grounding device consists of a grounding electrode (plate), a grounding busbar (indoor and outdoor), a grounding down-conductor (grounding jumper), and a frame grounding. It is used to realize the purpose of connecting the electrical system to the earth. The metal object that is in direct contact with the ground for electrical connection is the ground electrode. It can be an artificial ground electrode or a natural ground electrode. This grounding electrode can be assigned some electrical function, such as being used as system grounding, protective grounding or signal grounding. The grounding busbar is the reference potential point of the electrical installation of the building, through which the part that needs to be grounded in the electrical installation is connected to the grounding electrode. It also serves another function, that is, by interconnecting the equipotential bonding lines in the electrical installation, the overall equipotential bonding between the large conductive parts of a building is realized. The connection line between the grounding electrode and the grounding busbar is called the grounding electrode lead. Safety isolating transformer safety isolating transformer. Transformers that supply tools, other equipment and distribution circuits with safe extra-low voltage. Its input winding and output winding are electrically isolated by at least the equivalent of double insulation or reinforced insulation. Next, an excellent grounding device manufacturer, Sichuan Sunlight intelligent electric equipment Co., Ltd, will introduce the classification of grounding devices, basic concept of grounding device resistance and installation of grounding device. Classification of grounding devices The grounding device is composed of a grounding body (round steel, angle steel, flat steel, steel pipe, etc.) buried in the soil and a grounding wire for connection. According to the purpose of grounding, the grounding of electrical equipment can be divided into: working grounding, lightning protection grounding, protective grounding, and instrument control grounding. Working grounding: It is the grounding required to ensure the normal operation of the power system. For example, the neutral point of the transformer in the neutral point direct grounding system is grounded, and its function is to stabilize the potential of the power grid to the ground, thereby reducing the insulation to the ground. Lightning protection grounding: It is the grounding set for the needs of lightning protection. For example, the grounding of lightning rods (wires) (now called lightning rods, wires, strips) and arresters is to make the lightning current smoothly lead to the ground, so as to reduce the lightning overvoltage, so it is also called overvoltage protection grounding. Protection grounding device: also known as a safety grounding device, it is a grounding device set up for personal safety, that is, the electrical equipment shell (including the cable sheath) must be grounded to prevent the shell from being charged and endangering personal safety. Instrument control grounding device: the thermal control system, data acquisition system, computer monitoring system, transistor or microcomputer type relay protection system, and telecontrol communication system of the power plant, etc., are set up to stabilize the potential and prevent interference. Also known as an electronic system grounding device. The above is the classification of grounding devices. basic concept of grounding device resistance The resistance of the grounding device refers to the resistance encountered when the current passes through the grounding body into the earth and spreads around. The earth has a certain resistivity, and if there is current flowing through it, the earth has different potentials everywhere. After the current is injected into the ground through the grounding body, it spreads around in the form of a current field. 15~20m away), the resistance per unit diffusion distance and the current density in the ground are close to zero, and the potential here is zero. The curve U=f(r) in the figure represents the potential distribution on the ground surface (r represents the distance from the lightning current injection point). The above is the basic concept of grounding device resistance. Installation of grounding device


Is it permitted to use flexible conduit over 6 feet in length as a grounding means?

No. The new electrical code change does not allow any flexible conduit to be used as a ground means. It is now required to have a green ground wire pulled into the conduit with the other conductors in the flexible conduit. This grounded bonding conductor is not counted as wire fill when calculating the size of the flexible conduit to use


What to do with no ground in wall but ground wire in fixture?

Very often the ground wire in the fixture is ignored, or just connected to the box, if there isn't a conductor to connect to. This, however, is a code violation as any fixture with a ground wire is required to have it properly connected to an equipment grounding conductor back to the panel. This is for YOUR SAFETY. Technically you should rewire the circuit with the proper conductors. It is BAD PRACTICE to connect the ground wire to the neutral or white wire because this could create a hazard of its own.