Ground is sized based on the size of the feeder wire and not the amps of the service!
However, for a 600 amp service 1500MCM copper wire is one option (NEC 310.16) ;therefor, ground wire is 3/O copper (NEC 250.66)
or
another option is a two sets of 350 MCM copper wire then a #2 copper (since the biggest feeder wire is 350MCM).
Ground is sized based on the size of the feeder wire and not the amps of the service! However, for a 600 amp service 1500MCM copper wire is one option (NEC 310.16) ;therefor, ground wire is 3/O copper (NEC 250.66) or another option is a two sets of 350 MCM copper wire then a #2 copper (since the biggest feeder wire is 350MCM).
The required size of the service grounding conductor for a 350 amp parallel service will depend on the specific installation requirements and local codes. It is recommended to consult with a licensed electrician or engineer to determine the proper size based on factors such as the type of wiring used, the distance between the service entrance and the transformer, and the local ground conditions.
We recommend using a #6 copper wire for the connection between the breaker box and the earth ground rod. This size wire is commonly used for grounding purposes and is sufficient for carrying the electrical current safely to the ground rod. Be sure to consult with a qualified electrician to ensure the proper materials and installation for your specific situation.
For Service Entrance Cable 600 kcmill (Thousands of circular mils).
For a 200 amp service with a 60 foot run, it is recommended to use 3/0 AWG copper wire or 250 kcmil aluminum wire to ensure proper voltage drop and capacity for the load. Be sure to consult with local codes and a licensed electrician for specific requirements and installation guidance.
Notes: 1. Where multiple sets of service-entrance conductors are used as permitted in Section 230-40, Exception No. 2, the equivalent size of the largest service-entrance conductor shall be determined by the largest sum of the areas of the corresponding conductors of each set. 2. Where there are no service-entrance conductors, the grounding electrode conductor size shall be determined by the equivalent size of the largest service-entrance conductor required for the load to be served. 1 This table also applies to the derived conductors of separately derived ac systems. 2 See installation restrictions in Section 250-64(a).
A 1600 amp service typically requires 500 kcmil copper wire or 750 kcmil aluminum wire. It's important to consult with a qualified electrician to determine the exact size and type of wire needed for your specific installation to ensure safety and compliance with local electrical codes.
There is no one wire that is rated for 1800 amps. The service will have to be a quad parallel of the conductors. A 600 MCM conductor with an insulation factor of 90 degrees C is rated at 475 amps. This conductor paralleled into four equal lengths will give an ampacity of 1900 amps for each leg of the service.
This size service can be wired in a few combinations. Two parallel runs of 1250 MCM, three parallel runs of 600 MCM, four parallel runs of 350 MCM. Of the three choices the four runs of 350 MCM wires would be the easiest to handle if there are any bends in the service entrance conduit.
A 350 MCM copper conductor with an insulation rating of 90 degree C is rated at 350 amps.
For 600 amps, you would typically need at least a 250 MCM wire size to safely handle the current without overheating. It's recommended to consult with a professional electrician to determine the specific wire size needed based on the application and local electrical codes.
For a single phase 600 amp service, you would typically use 350 kcmil conductors. However, the specific size can depend on factors like voltage drop calculations, distance from the utility transformer, and ambient temperature. It's always recommended to consult with a qualified electrician or electrical engineer for a precise determination.