For a 400 amp service entrance, a grounding conductor of at least 3/0 AWG (American Wire Gauge) copper or 250 kcal (thousand circular mils) aluminum is required, in compliance with electrical codes and regulations. However, specific requirements may vary based on local codes and the specific conditions of the installation, so it's important to consult with a qualified electrician or refer to the applicable building codes for precise guidance.
The size of grounded conductor that is required for 400 amps will vary depending on the circuit. A person should consult with their electric company before attempting to wire the circuit themselves.
<<>>
No conductor smaller than #6 bare shall be used for a ground wire. 2006 code book called for #3 copper for a 400 amp service.
It actually depends on the size of service entrance feeders. 1/0 copper should cover you in most cases
As a service entrance wire you need AWG # 3/0 gauge copper.
A #6 copper ground conductor would be needed.
Use AWG #1 copper service entrance wire and #4 copper ground wire.
#6 bare copper wire.
Notes: 1. Where multiple sets of service-entrance conductors are used as permitted in Section 230-40, Exception No. 2, the equivalent size of the largest service-entrance conductor shall be determined by the largest sum of the areas of the corresponding conductors of each set. 2. Where there are no service-entrance conductors, the grounding electrode conductor size shall be determined by the equivalent size of the largest service-entrance conductor required for the load to be served. 1 This table also applies to the derived conductors of separately derived ac systems. 2 See installation restrictions in Section 250-64(a).
As a service entrance wire you need AWG # 3/0 gauge copper.
200 amp service in chicago uses 3 aught.
A #6 copper ground conductor would be needed.
Use AWG #1 copper service entrance wire and #4 copper ground wire.
The wire size used in a service entrance distribution panel is governed by the size of the services over current device. The larger the service, the larger the fault current could be, the larger the ground wire to carry the fault current to ground. If the largest service conductor carries 100 amps use a #8, 200 amps - #6, 400 amps - #3, 600 amps - #1, 800 amps - 1/0 and over 800 amps - 2/0 for the ground wire. <<>> Golden Valley Electric Assoc. in Alaska requires #4AWG copper wire for a ground from the breaker box to earth ground rod. The same goes from the service entrance panel on the pole.
#6 bare copper wire.
Notes: 1. Where multiple sets of service-entrance conductors are used as permitted in Section 230-40, Exception No. 2, the equivalent size of the largest service-entrance conductor shall be determined by the largest sum of the areas of the corresponding conductors of each set. 2. Where there are no service-entrance conductors, the grounding electrode conductor size shall be determined by the equivalent size of the largest service-entrance conductor required for the load to be served. 1 This table also applies to the derived conductors of separately derived ac systems. 2 See installation restrictions in Section 250-64(a).
2 AWG Aluminum.
It is the installation of ground rods at a service entrance distribution to bring the relative resistance to ground to be within 5 ohms of the utility's distribution network. This grounding system is then connected to the service distribution with a calculated size wire and connected to the distribution at a point within the distribution panel, where the service neutral wire joins the neutral bus bar.
The wire that is used for connecting the ground rod or plate to the electrical distribution is governed by the size of the electriclal distribution. In Canada a #6 bare copper is the minimum size for a 200 amp service.
To calculate the wire size, a system voltage is needed.
Service entrance wire should be AWG #3 copper.