A 40 amp breaker is used in conjunction with AWG # 8 copper wire. The black and red wires are connected to the breaker. The ground wire is connected to the ground bar and the white wire is connected to the neutral bar.
A #8 copper conductor with an insulation factor from 75 to 90 degrees C is rated at 45 amps.
AWG # 8 wire.
Number 8 awg
If you are referring to house wiring then the answer is no. A breaker protects the wire size that is connected to the breaker. In home wiring most homes are wired with a #14 wire which is rated at 15 amps. That is why the wire is protected by a 15 amp breaker. The correct wire size to connect to a 40 amp breaker is a #8. This size wire is too large to connect to receptacles an light fixture terminals.
A #8 aluminium wire with an insulation factor of 90 degrees C is rated at 45 amps.
A 30 amp breaker run 75 feet would require you use AWG #10 wire. But, an oven normally pulls more that 30 amps and I would not use #10 wire on a 30 amp breaker for an oven. Normally any newer oven is wired with AWG #6 gauge wire on a 50 amp circuit breaker so the breaker will not trip during heavy use of the oven. Some older ovens could use a #8 wire on a 40 amp breaker.
Not unless you change the wiring for that circuit. The breaker protects the wiring and if you install a 40 amp breaker on a 15 amp wire circuit you will have a fire in your home.
I think you mean 2 HP pump. I am assuming a 220 To 240 volt supply and that should equate to about a 12 amp current. All my pumps use only a 30 amp breaker and 10 AWG wire.
Depends on the size of the wire going to the A/C. If the wire is AWG #10 you cannot install a 40 amp breaker. If the wire is AWG #8 you can.
Look on the heater and see what amps it is pulling. That will determine the wire size and breaker size. It must be on a dedicated circuit. 15 amps = AWG # 14 wire with 15 amp breaker 20 amps = AWG # 12 wire with 20 amp breaker 30 amps = AWG # 10 wire with 30 amp breaker 40 amps = AWG # 8 wire with 40 amp breaker
No. The 20 amp breaker is probably protecting a #12 wire. Connecting a 40 amp breaker to the 20 amp #12 wire would seriously overload the #12 wire. This means that if the load increased to a full 40 amps the insulation on the smaller size wire would most likely melt off and the wire could short out.
If you are referring to house wiring then the answer is no. A breaker protects the wire size that is connected to the breaker. In home wiring most homes are wired with a #14 wire which is rated at 15 amps. That is why the wire is protected by a 15 amp breaker. The correct wire size to connect to a 40 amp breaker is a #8. This size wire is too large to connect to receptacles an light fixture terminals.
Minimum size is 10 gauge with a 30 amp breaker. To be safe I would install an 8 gauge with a 40 amp breaker.
A #8 aluminium wire with an insulation factor of 90 degrees C is rated at 45 amps.
40 amp
No a #12 wire is only rated for 20 amps. The 40 amp breaker will not protect the #12 wire. A 40 amp breaker should have a #8 wire connected to it which is rated at 45 amps. The only time that a breaker is allowed to be bigger that the wire size rating according to the electrical code is when a motor is connected to the breaker. This is to stop the 300 percent inrush of the motor full load amps from nuisance tripping a smaller sized breaker.
In the United States, if the wire is #8 copper or larger (smaller number) it will work fine on a 40 amp breaker. If the wire is #10 copper, there is something wrong with the breaker if it does not fit. Pull the breaker out of the panel and look into where the wire terminates to see why the #10 wire won't fit.
A 30 amp breaker run 75 feet would require you use AWG #10 wire. But, an oven normally pulls more that 30 amps and I would not use #10 wire on a 30 amp breaker for an oven. Normally any newer oven is wired with AWG #6 gauge wire on a 50 amp circuit breaker so the breaker will not trip during heavy use of the oven. Some older ovens could use a #8 wire on a 40 amp breaker.
Not unless you change the wiring for that circuit. The breaker protects the wiring and if you install a 40 amp breaker on a 15 amp wire circuit you will have a fire in your home.
Wire size is rated by Amperes of current. You did not mention the wire size of the aluminum wire, so there is no way to answer your question. The voltage rating is more a rating of how good the insulation around the wire is.