answersLogoWhite

0


Best Answer

A #6 copper wire with an insulation factor of 75 or 90 degrees C is rated at 65 amps.

User Avatar

Wiki User

13y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

15y ago

#6 copper

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What wire should you use for 50 amp?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

What size ground wire should I use for a 50 amp hot tub panel?

# 10 bare copper.


Can you use 8 three wire for a 50 Amp breaker to an oven range?

No .


What size wire to use with 50 amp 480v 3 phase so cord size?

6


Can 50 Amp breaker replace 45 Amp breaker?

Both a 45 amp and 50 amp breaker would require 6 AWG wire. So if you have 6 AWG wire and any devices like an outlet are rated at 50 amps or greater you are okay.


Will my electrician need to run new wire from the outlet to the circuit breaker to change from a 50 amp to a 60 amp outlet?

Maybe not. Since there is no wire with a rating of 50 amps exactly there may be 60 amp wire already installed. Range's use a #8 wire with 50 amp range receptacle for its circuit. If the wire that is installed now is # 6, that is good for 65 amps, then no wire needs to be changed. The only 60 amp receptacle that will be allowed on the 60 amp cable is a three pole four wire grounding 125/250 volt device. The number will be 14-60R. There is a three phase rated receptacle in the three pole four wire grounding type. It is a 15-60R.


What size breaker should be used for a double oven?

50 amp breaker wired with AWG # 6 wire.


Can you change a 50 amp receptacle to a 15 amp receptacle?

Yes as long as you change the 50 amp breaker to a 15 amp breaker. You will be hard pressed to get the 50 amp #6 wire under the terminals of the 15 amp receptacle.


What size wire for 75 feet of wire for a 30 amp 220 volt oven?

A 30 amp breaker run 75 feet would require you use AWG #10 wire. But, an oven normally pulls more that 30 amps and I would not use #10 wire on a 30 amp breaker for an oven. Normally any newer oven is wired with AWG #6 gauge wire on a 50 amp circuit breaker so the breaker will not trip during heavy use of the oven. Some older ovens could use a #8 wire on a 40 amp breaker.


What all can you use 6 3 wire for?

I just used it to run my 50 amp electric stove. You can use it for a small sub-panel.


240v nema6-50r outlet wired with 6 gauge wire and 50 amp breaker you need to run a heater with a nema 6-30p can you simply put a 30 amp receptical in place of the 50 amp receptical?

Not legally because the rating of the 30 amp receptacle would have a 50 amp breaker ahead of it. If you reduced the feed breaker to 30 amps and still use the #6 wire, this would be within the electrical code rules.


Can a 100 amp main have 2 50 amp breakers?

Yes.Additional InformationBreakers and fuses protect the wires to prevent fire. The 100 Amp breaker in the meter base (main) protects the wire from the meter base to the breaker panel. The 50 Amp breaker in the breaker panel protects the wire from the breaker panel to the outlet. Sometimes the 100 amp main breaker is located in the panel.If you are asking "Can you use two 50 amp breakers for the main breakers with a 100 amp service, then yes you can. The National Electrical Code allows you to use up to 6 breakers as the main overcurrent protection.


Can you use 6-3 NM wire and 50 amp breakers and 50 amp range cord for a 40 amp max load range?

You can if you have the existing materials. If you want to keep your costs down the same installation can be installed with the following materials. For wire all that is needed is 3C #8 wire. For the breaker a two pole 40 amp will work. You will need a 4 11/16" square box to install the range receptacle into.