The equation for amperage is I = W/E, Amps = Watts/Volts. The amperage for the furnace would be, Amps = 15000/240 = 62.5 amps. So to answer the question, yes a 100 amp breaker with a #4 copper conductor will be sufficient to operate a 15 kW furnace. A 70 amp breaker will work but it is cutting the edge a bit too fine as you don't need the furnace to trip off during the winter months (northern hemisphere) if you are away from your home for an extended period of time.
The amperage capacity of the main bus bars and the connection of the main breaker to the bus bars.
No. Power to all the circuit breakers will be cut off except for the Main power breaker. The Main power breaker (which supplies power to all other breakers and will say 100, or whatever your max breaker box power is, on it )will have power going to it all the time, unless power is turned off outside the house.
You can reduce the breaker size because that limits the current that can reach the main panel. There is no safety issue other than the significant danger in an unskilled person changing out a main breaker.
For a 100 Amp breaker panel it would be 2 AWG. For 150 Amps it would require 2/0 (2 ought) aluminum wire.
Breaker boxes do not have fuses associated with them unless the main disconnect is independent from the breaker box. If that is the case both fuses have to be the same in the main disconnect that protects the breaker box.
Simple. Your main electrical panel will have a "main breaker". This will be a two pole breaker, usually at the top of the panel. It will have a number on the breaker "handle" such as 150 or 200. This is the maximum number of amps your panel can supply. Most newer homes, 1975 and newer have a 200 amp service.
Yes, a blown fuse can cause your furnace to not turn on. Check the breaker box and see if any of them have tripped.
Tss Cause there's a bunch of bee's in there or sumthin Tss
The amperage capacity of the main bus bars and the connection of the main breaker to the bus bars.
100
You can typically determine the amperage of an electrical panel by looking at the main breaker. A 100 amp panel will have a main breaker rated at 100 amps, while a 200 amp panel will have a main breaker rated at 200 amps. Additionally, the size and number of circuit breaker slots can also be indicators of the amperage rating.
Its not recommended because your new main breaker will allow up to 100 amps and your old wire can only safely handle 60amps. If you put a 60amp main breaker in the new box, that would be acceptable. No, it is perfectly safe. Because the box is overrated, there is no problem. If the box is the main panel, and not a subpanel, install a 60A main breaker so you cannot overload your service. If it is a subpanel this 60A breaker should be in the main panel.
To replace breakers in an electrical box it is extremely important the replace the breaker with the same wattage. Do not replace a 100 breaker with a 20 breaker is can cause damage.
I'm not sure why your furnace would shut off after a power outage but first check your breaker in the breaker box to make sure it is in the on position. If this is not the problem remove the cover on furnace and look for a red reset button on the pump. Press this button and hold for a second or two and you furnace should restart. If however it shuts down again you have other problems and will need a furnace repairman.
The range on a breaker box refers to the maximum amount of electrical current that the circuit breaker can handle before it trips and shuts off power to the circuit. It is important to not exceed the range to prevent electrical hazards and damage to the electrical system.
The main breaker will have marking indicating size of electrical service, or if it is a fuse system....the fuses will have current ratings. If it is a subpanel, it might not have a main breaker. In this case you would have to look in the panel that the feed is coming from and find the size of the breaker that is feeding it. In either case you must look for the manufacturer's label that will have the maximum current the panel can handle, make sure the breaker feeding the panel doesn't exceed this rating.
That's pushing it but it can work. It depends if you have central A/C, electric range, water heater, etc. Those are your amp suckers. You'll need to be mindful when operating the hot tub; not running the dryer, oven, or other large appliances.