A dryer requires a 30 amp receptacle. This will be to receive a four blade dryer plug. The wire needed will be a three copper wire #10 cable set with a bare #14 copper ground wire. The breaker will be a two pole 30 amp breaker.
You never, ever mix wire sizes within a circuit. However you can wire a 30 amp circuit using AWG # 8/3 wire, although that is overkill and AWG #10 wire is what you would normally use on a 30 amp circuit.
the size of the wire that you need to run depends on the the amperage of the device/appliance you'll be hooking up to that line. Use #12 wire for 20 amp, #10 for 30 amp, #8 wire for 40 amps and #6 for 50 amps. Hope that helps.
#10 wire is used on a 30 amp service.
A 30 amp breaker run 75 feet would require you use AWG #10 wire. But, an oven normally pulls more that 30 amps and I would not use #10 wire on a 30 amp breaker for an oven. Normally any newer oven is wired with AWG #6 gauge wire on a 50 amp circuit breaker so the breaker will not trip during heavy use of the oven. Some older ovens could use a #8 wire on a 40 amp breaker.