Use a 30 amp breaker.
Chat with our AI personalities
Not unless the wire going to the refrigerator outlet is AWG 10/2. If it is wired with 12/2 wire then you must use a 20 amp breaker. Using a 30 amp breaker is dangerous and a fire hazard.
The size breaker you use is determined by the size wire used in the circuit. If you use AWG #12/2 wire then use a 20 amp breaker. If you use AWG # 14/2 then use a 15 amp breaker.
A #10 wire has the capacity for 30 amps. No breaker larger than 30 amps should be used to protect the circuit.
It is not the number of bulbs that you worry about. It is the wire size that is your concern. If the circuit is wired with AWG 12/2 wire then use a 20 amp breaker. If it is wired with a AWG 14/2 wire then use a 15 amp breaker. You are protecting the wiring with the correct size breaker.
I think you mean 2 HP pump. I am assuming a 220 To 240 volt supply and that should equate to about a 12 amp current. All my pumps use only a 30 amp breaker and 10 AWG wire.