For a 400 amp service entrance, a grounding conductor of at least 3/0 AWG (American Wire Gauge) copper or 250 kcal (thousand circular mils) aluminum is required, in compliance with electrical codes and regulations. However, specific requirements may vary based on local codes and the specific conditions of the installation, so it's important to consult with a qualified electrician or refer to the applicable building codes for precise guidance.
As a service entrance wire you need AWG # 3/0 gauge copper.
A #6 copper ground conductor would be needed.
Use AWG #1 copper service entrance wire and #4 copper ground wire.
#6 bare copper wire.
Notes: 1. Where multiple sets of service-entrance conductors are used as permitted in Section 230-40, Exception No. 2, the equivalent size of the largest service-entrance conductor shall be determined by the largest sum of the areas of the corresponding conductors of each set. 2. Where there are no service-entrance conductors, the grounding electrode conductor size shall be determined by the equivalent size of the largest service-entrance conductor required for the load to be served. 1 This table also applies to the derived conductors of separately derived ac systems. 2 See installation restrictions in Section 250-64(a).
As a service entrance wire you need AWG # 3/0 gauge copper.
200 amp service in chicago uses 3 aught.
A #6 copper ground conductor would be needed.
Use AWG #1 copper service entrance wire and #4 copper ground wire.
From the question it is hard to establish whether the service size is 350 amps or the service conductors are 350 MCM in parallel. If the service is 350 amps, the grounding conductor is #3 bare copper wire. Parallel 350 MCM conductors will allow for a 600 amp service. The grounding conductor for a 600 amp service is a #1 bare copper wire.
The recommended size for a 100 amp service entrance cable is typically 2 AWG copper or 1/0 AWG aluminum.
#6 bare copper wire.
Notes: 1. Where multiple sets of service-entrance conductors are used as permitted in Section 230-40, Exception No. 2, the equivalent size of the largest service-entrance conductor shall be determined by the largest sum of the areas of the corresponding conductors of each set. 2. Where there are no service-entrance conductors, the grounding electrode conductor size shall be determined by the equivalent size of the largest service-entrance conductor required for the load to be served. 1 This table also applies to the derived conductors of separately derived ac systems. 2 See installation restrictions in Section 250-64(a).
The recommended cable size for a 200 amp service entrance is typically 2/0 AWG copper or 4/0 AWG aluminum.
2 AWG Aluminum.
It is the installation of ground rods at a service entrance distribution to bring the relative resistance to ground to be within 5 ohms of the utility's distribution network. This grounding system is then connected to the service distribution with a calculated size wire and connected to the distribution at a point within the distribution panel, where the service neutral wire joins the neutral bus bar.
The wire that is used for connecting the ground rod or plate to the electrical distribution is governed by the size of the electriclal distribution. In Canada a #6 bare copper is the minimum size for a 200 amp service.