The size called for is one ought (0). There are addendum to this rule depending on where you live in the country. Check the addendum to this code rule in your area.
For a 400 Amp service with 500 MCM conductors, the minimum size grounding electrode conductor required would be 3/0 AWG copper or 250 kcmil aluminum based on the NEC Table 250.66.
From the question it is hard to establish whether the service size is 350 amps or the service conductors are 350 MCM in parallel. If the service is 350 amps, the grounding conductor is #3 bare copper wire. Parallel 350 MCM conductors will allow for a 600 amp service. The grounding conductor for a 600 amp service is a #1 bare copper wire.
# A ground electrode conductor is a conductor that originates at the neutral or equipment ground buses in the main service entrance panel board or separating derived system (e.g. isolation transformer) # A ground electrode is a item that is in contact with the earth (e.g. Building metal frame, underground continuous metallic water pipe etc...) # A ground conductor is a conductor that is used to keep an electrical system continuous. Ground conductors are required, by code, in all PVC conduit runs. Ground conductors are also used to keep all metallic components of the installation at the same zero potential to overcome mechanical connections that would not carry a fault current back to the supply distribution panel.
grounding material is not a good word but as short as possible is a good answer the entrance panel must be connected to the best possible ground this is called the grounding electrode the grounding electrode conductor connects to the ground bar in the entrance panel if the panel has a a neutral the neutral bar can be bonded to the ground bar Grounding electrodes form best to worse well casing water pipe (NOT plastic) buried plates or wire grid or bonded reinforcing steel driven rod if you are talking about distances to the panel it should be centered about shoulder height doors need to have about 2' of clearance in all directions weather open or shut
Typically for a 200A service, a #4 copper wire or a #2 aluminum wire is used for the grounding conductor. It is important to follow local electrical codes and consult with a licensed electrician for specific requirements.
The grounding electrode conductor size chart provides information on the recommended size of the conductor based on the type of grounding electrode and the size of the service entrance conductor.
500 mcm
For a 400 Amp service with 500 MCM conductors, the minimum size grounding electrode conductor required would be 3/0 AWG copper or 250 kcmil aluminum based on the NEC Table 250.66.
From the question it is hard to establish whether the service size is 350 amps or the service conductors are 350 MCM in parallel. If the service is 350 amps, the grounding conductor is #3 bare copper wire. Parallel 350 MCM conductors will allow for a 600 amp service. The grounding conductor for a 600 amp service is a #1 bare copper wire.
NO some armored cable has a ground some sealtite has copper in the helix wit the drain shield some liquite has no conduction at all all armor is a helix which is a coil and acts as insulation at hi frequency xlpe cross linked polyethylene is an insulator service cable is never used for grounding grounding electrode conductor grounding equipment conductor grounding conductor are all separate from service cables if a tall trucks hits an overhead cable you dont want to lose the ground in short NO
The grounding conductor of a service distribution is sized by the ampacity of the service. By just stating the wire size, this does not give this information, as many variables enter into what wires are used depending on length, ambient temperature and insulation factor to name a few.
It is the conductor that is used in service distribution panels that bonds the distribution panel's neutral bus bar to the ground electrode (rod). This brings all of the distribution panel neutrals that are connected to the same supply system to the same potential, that being zero. Should a supply service neutral open this ground wire will maintain the systems integrity until repairs can be made.
In Canada the grounding electrode requirement is for two steel 5/8" x 10' copper clad rods spaced 10 feet apart.
For service sizes of 100 amps and less a #8 bare copper conductor is required.
For a 200 amp service, typically, at least two grounding electrodes are required. These can include a ground rod, a concrete-encased electrode, or other approved grounding methods, depending on local code requirements. Additionally, a separate equipment grounding conductor is needed to ensure safety. Always check the National Electrical Code (NEC) and local regulations for specific requirements.
# A ground electrode conductor is a conductor that originates at the neutral or equipment ground buses in the main service entrance panel board or separating derived system (e.g. isolation transformer) # A ground electrode is a item that is in contact with the earth (e.g. Building metal frame, underground continuous metallic water pipe etc...) # A ground conductor is a conductor that is used to keep an electrical system continuous. Ground conductors are required, by code, in all PVC conduit runs. Ground conductors are also used to keep all metallic components of the installation at the same zero potential to overcome mechanical connections that would not carry a fault current back to the supply distribution panel.
Hi ,my name isBob,and i want to know what is the minim amperage required for one commercial space 1020.00 sq Ft ? is going to be like an restaurant. Very respectfully, Bob