β 14y agoThe size called for is one ought (0). There are addendum to this rule depending on where you live in the country. Check the addendum to this code rule in your area.
Wiki User
β 14y agoFor an 800 amp service with parallel sets of 500 kcmil copper conductors, the grounding electrode conductor size should be based on the largest conductor in the parallel set. The grounding electrode conductor size should be sized based on Table 250.66 in the NEC, which recommends a minimum size of 3/0 AWG copper for 1/0 AWG or larger service-entrance conductors.
For a 400 Amp service with 500 MCM conductors, the minimum size grounding electrode conductor required would be 3/0 AWG copper or 250 kcmil aluminum based on the NEC Table 250.66.
The required size of the service grounding conductor for a 350 amp parallel service will depend on the specific installation requirements and local codes. It is recommended to consult with a licensed electrician or engineer to determine the proper size based on factors such as the type of wiring used, the distance between the service entrance and the transformer, and the local ground conditions.
A ground conductor is a wire that connects electrical devices to the ground terminal in an electrical system, providing a path for fault currents. A ground electrode conductor, on the other hand, is a wire that connects the ground electrode (such as a grounding rod) to the ground terminal, allowing for the dissipation of electrical charges into the earth.
The clearance from a service entrance panel to grounding material should typically be at least 3 feet to ensure proper safety measures against electrical hazards. This distance helps prevent accidental contact and ensures effective grounding of the electrical system. It is important to adhere to local building codes and regulations which may specify specific clearance requirements for your area.
Typically for a 200A service, a #4 copper wire or a #2 aluminum wire is used for the grounding conductor. It is important to follow local electrical codes and consult with a licensed electrician for specific requirements.
500 mcm
For a 400 Amp service with 500 MCM conductors, the minimum size grounding electrode conductor required would be 3/0 AWG copper or 250 kcmil aluminum based on the NEC Table 250.66.
The required size of the service grounding conductor for a 350 amp parallel service will depend on the specific installation requirements and local codes. It is recommended to consult with a licensed electrician or engineer to determine the proper size based on factors such as the type of wiring used, the distance between the service entrance and the transformer, and the local ground conditions.
NO some armored cable has a ground some sealtite has copper in the helix wit the drain shield some liquite has no conduction at all all armor is a helix which is a coil and acts as insulation at hi frequency xlpe cross linked polyethylene is an insulator service cable is never used for grounding grounding electrode conductor grounding equipment conductor grounding conductor are all separate from service cables if a tall trucks hits an overhead cable you dont want to lose the ground in short NO
The grounding conductor of a service distribution is sized by the ampacity of the service. By just stating the wire size, this does not give this information, as many variables enter into what wires are used depending on length, ambient temperature and insulation factor to name a few.
It is the conductor that is used in service distribution panels that bonds the distribution panel's neutral bus bar to the ground electrode (rod). This brings all of the distribution panel neutrals that are connected to the same supply system to the same potential, that being zero. Should a supply service neutral open this ground wire will maintain the systems integrity until repairs can be made.
In Canada the grounding electrode requirement is for two steel 5/8" x 10' copper clad rods spaced 10 feet apart.
For service sizes of 100 amps and less a #8 bare copper conductor is required.
A ground conductor is a wire that connects electrical devices to the ground terminal in an electrical system, providing a path for fault currents. A ground electrode conductor, on the other hand, is a wire that connects the ground electrode (such as a grounding rod) to the ground terminal, allowing for the dissipation of electrical charges into the earth.
The clearance from a service entrance panel to grounding material should typically be at least 3 feet to ensure proper safety measures against electrical hazards. This distance helps prevent accidental contact and ensures effective grounding of the electrical system. It is important to adhere to local building codes and regulations which may specify specific clearance requirements for your area.
Hi ,my name isBob,and i want to know what is the minim amperage required for one commercial space 1020.00 sq Ft ? is going to be like an restaurant. Very respectfully, Bob
Answer for USA, Canada and countries running a 60 Hertz supply service.CEC states that a #3 bare copper conductor is a common grounding conductor size for a 200 amp service panel and it is the minium size for service raceway and service equipment of 400 amps.