The National Electrical Code (US) allows up to thirteen 20 amp receptacles on a 20 amp circuit.
120V x 20A = 2400 VA
each duplex receptacle is calculated at 180 VA
2400 / 180 = 13.3333 receptacles, since you can't put a third of a receptacle in, you have to round down to 13.
There are typically 8 to 10 receptacles on most house circuits with special applications in Kitchens. The wires are in parallel with Black to Black, White to White and Bare Wire Ground to Ground.
It is perfectly acceptable to have (2) 120 volt 15 amp receptacles operated from a 120 volt 20 amp circuit breaker (as a general rule of thumb 11 receptacles are acceptable on a 20 amp circuit). The 15 amp rating of the receptacle is the maximum allowed amperage that should be hooked up to the receptacle at any one time. So in this case the limiting factor is the amount of current being drawn across both receptacles simultaneously should not exceed the 20 amp rating of the circuit breaker. In the United States the NEC code allows the use of a 20 amp circuit breaker to feed a branch circuit consisting of 15 amp receptacles. Generally you would not exceed 11 receptacles though as you will assume an average load of 1.5 amps per receptacle and trying to maintain about 80% max load.
The kitchen and garage are the only 20 amp circuts usually.
To calculate the load for receptacles, first determine the total number of receptacles on the circuit. Typically, the National Electrical Code (NEC) allows for a load of 180 watts per duplex receptacle. Multiply the number of receptacles by 180 watts, then divide by the voltage (usually 120V in residential settings) to find the total amperage load. It's essential to consider the diversity factor and any additional loads connected to the circuit for a more accurate assessment.
Receptacles are daisy chained so that one receptacle also powers others. A GFCI is often in the first receptacle so that a fault on any other connection/receptacle will be detected and cut off by that GFCI. Trip the GFCI. Then find all receptacles and appliances now without power. A fault can be in any one or due to a combination of many slightly defective appliances.
There are typically 8 to 10 receptacles on most house circuits with special applications in Kitchens. The wires are in parallel with Black to Black, White to White and Bare Wire Ground to Ground.
All receptacles in a garage must be GFCI protected by code. Typically, the first receptacle in the circuit (location is irrelevant) must be a GFCI, then all others down stream in the circuit will be protected, and can be common receptacles.
It is perfectly acceptable to have (2) 120 volt 15 amp receptacles operated from a 120 volt 20 amp circuit breaker (as a general rule of thumb 11 receptacles are acceptable on a 20 amp circuit). The 15 amp rating of the receptacle is the maximum allowed amperage that should be hooked up to the receptacle at any one time. So in this case the limiting factor is the amount of current being drawn across both receptacles simultaneously should not exceed the 20 amp rating of the circuit breaker. In the United States the NEC code allows the use of a 20 amp circuit breaker to feed a branch circuit consisting of 15 amp receptacles. Generally you would not exceed 11 receptacles though as you will assume an average load of 1.5 amps per receptacle and trying to maintain about 80% max load.
Answer for USA, Canada and countries running a 60 Hertz supply service.Yes, if it is connected with a three wire circuit such as kitchen counter receptacles. In this case both top and bottom of the duplex receptacle are dedicated circuits. An example of a duplex receptacle being the only device in the circuit from a 15 amp breaker is the receptacle for a microwave oven.
The kitchen and garage are the only 20 amp circuts usually.
To calculate the load for receptacles, first determine the total number of receptacles on the circuit. Typically, the National Electrical Code (NEC) allows for a load of 180 watts per duplex receptacle. Multiply the number of receptacles by 180 watts, then divide by the voltage (usually 120V in residential settings) to find the total amperage load. It's essential to consider the diversity factor and any additional loads connected to the circuit for a more accurate assessment.
Receptacles are daisy chained so that one receptacle also powers others. A GFCI is often in the first receptacle so that a fault on any other connection/receptacle will be detected and cut off by that GFCI. Trip the GFCI. Then find all receptacles and appliances now without power. A fault can be in any one or due to a combination of many slightly defective appliances.
If the 2 hot wires are connected to either side of a receptacle, you have a 240v receptacle (assuming it's in the US). This is typically done for window air conditioners. But code requires that the receptacle have a different configuration than other receptacles in the building so you don't run the risk of plugging in a 120v device into a 240v receptacle.
A 20-amp circuit can typically support up to 10 receptacles.
No. This practice is a violation of Article 210.19 (A) of the NEC. "Conductors of branch circuits supplying more than one receptacle for cord-and-plug-connected portable loads shall have an ampacity of not less than the rating of the branch circuit."
The most common types are the regular type, where the only over current protection is provided by the breaker panel. the other most common type is the GFCI (Ground Fault Circuit Interrupter) This type has a built in "circuit breaker" so when it senses a fault in the circuit it trips-this type is the safest as they are more sensitive than circuit breakers in the breaker panel.See related links below.
Answer for USA, Canada and countries running a 60 Hz supply service.Allow for 1 amp per receptacle and then load the circuit to 80% of maximum.In the US and in every building except homes, code limits you to 13 receptacles per 20 amp circuit. In a home there is no limit because it is assumed that even if you put a receptacle on every stud, you couldn't possibly use them all.Further informationIn the United States in non-dwellings a circuit is limited to the number of receptacles a circuit can handle, calculating 180watts per duplex. This places a 13 receptacle limit on 20 amp / 120v circuits and a 10 receptacle limit on 15 amp / 120v circuits.In dwellings there is no limit on the number of receptacles that may be placed on one circuit since it is highly improbable that you could overload a residential circuit under normal circumstances.In dwelling kitchens, while there is still no limit in the number of receptacles, there is a requirement that counter tops be served by AT LEAST 2 SMALL APPLIANCE CIRCUITS RATED 20 AMPS.As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.Before you do any work yourself,on electrical circuits, equipment or appliances,always use a test meter to ensure the circuit is, in fact, de-energized.IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOBSAFELY AND COMPETENTLYREFER THIS WORK TO QUALIFIED PROFESSIONALS.