19 - 20 amps is too much. 16 amps is the maximum safe load for a circuit protected by a 20 amp breaker. Of course, its all safe, since the breaker will trip to prevent an overload from starting a fire. But current above 16 amps will eventually (sometimes after several hours even) trip the breaker.
If each outlet draws less than 2 amps, then you could control 10 outlets with a 20 amp GFCI outlet on a 20 amp circuit. However, it's worth consulting an electrician to ensure the load calculations are accurate and the wiring is safe for the intended use.
Yes, you can use lower amperage outlets - the problem would come if you were trying to run a 20 amp appliance on a 15 amp circuit or plug a 20 amp appliance into a 15 amp outlet. It would be better, though, as some kitchen appliances could exceed 15 amps (toaster ovens, some coffee makers, electric griddles, etc.) could try to draw more than the 15 amps your outlets are designed for. Perhaps you could get some 20 amp outlets and use those 15's in a hallway or something less likely to have high amperage draw.
Rule of thumb is about 8 unless it is a dedicated circuit. The NEC has no requirements on the number of receptacles that can be on a circuit in a residential setting. The circuit should be layed out to only cover 500 sq. feet. A single room of 500 sq. feet, you could put as many receptacle as you want on one circuit.
Branch circuit loading In Canada the CEC states that there shall be not more than 12 outlets on any 2-wire branch circuit. These outlets shall be considered to be rated at not less than 1 amp per outletWhere the connected load is known, the number of outlets shall be permitted to exceed 12, provided that the load current does not exceed 80% of the rating of the over current device protecting the circuit. For example on a 15 amp breaker, 15 x 80% = 12 amps, hence the standard of 12 outlets on any 2-wire branch circuit.On a 20 amp breaker, 20 x 80% = 16 amps. So from a 20 amp breaker this allows 16 outlets on a 2-wire branch circuit as long as the outlets are not considered to be rated at less than 1 amp per outlet.The definition of an outlet is a point in the wiring installation at which current is taken to supply utilisation equipment. What this means is that if a light switch and a fixture outlet were on the same 2-wire branch circuit they would be subtracted from the maximum count of 12 receptacle outlets on the circuit which would leave 10.If the light fixture draws 3 amps plus the switch outlet, then the total circuit outlet count would be reduced to 8 receptacle outlets (12 – 3 – 1 = 8).On a standard specification home most electricians will wire one circuit per room, the outlet count usually never reaches the maximum of 12 outlets.
No, the six outlets are not amperage rated to be connected to a 20 amp circuit. A normal 15 amp receptacle can not be protected by a 20 amp breaker. Change the 20 amp breaker to a 15 amp breaker. This combination will pass code regulations. =============== In the United States, in a home, you can connect two hard-wired (not cord and plug connected) fans and six receptacles (outlets) to a single 20 amp circuit provided the 2 fans do not draw more than 10 amps together. If they are cord and plug connected, this limitation on the fans does not apply. In commercial and industrial installations, power to hard-wired equipment is provided on different circuits than receptacles.
If each outlet draws less than 2 amps, then you could control 10 outlets with a 20 amp GFCI outlet on a 20 amp circuit. However, it's worth consulting an electrician to ensure the load calculations are accurate and the wiring is safe for the intended use.
Yes, you can use lower amperage outlets - the problem would come if you were trying to run a 20 amp appliance on a 15 amp circuit or plug a 20 amp appliance into a 15 amp outlet. It would be better, though, as some kitchen appliances could exceed 15 amps (toaster ovens, some coffee makers, electric griddles, etc.) could try to draw more than the 15 amps your outlets are designed for. Perhaps you could get some 20 amp outlets and use those 15's in a hallway or something less likely to have high amperage draw.
For a home, to calculate the amount of receptacle outlets on a 15 amp circuit, each receptacle outlet should be calculated as not drawing more than one amp each.
Typically, you can install multiple GFCI outlets on one circuit, but it is recommended to consult with a licensed electrician to ensure proper installation and safety.
Rule of thumb is about 8 unless it is a dedicated circuit. The NEC has no requirements on the number of receptacles that can be on a circuit in a residential setting. The circuit should be layed out to only cover 500 sq. feet. A single room of 500 sq. feet, you could put as many receptacle as you want on one circuit.
Branch circuit loading In Canada the CEC states that there shall be not more than 12 outlets on any 2-wire branch circuit. These outlets shall be considered to be rated at not less than 1 amp per outlet Where the connected load is known, the number of outlets shall be permitted to exceed 12, provided that the load current does not exceed 80% of the rating of the over current device protecting the circuit. For example on a 15 amp breaker, 15 x 80% = 12 amps, hence the standard of 12 outlets on any 2-wire branch circuit. On a 20 amp breaker, 20 x 80% = 16 amps. So from a 20 amp breaker this allows 16 outlets on a 2-wire branch circuit as long as the outlets are not considered to be rated at less than 1 amp per outlet. The definition of an outlet is a point in the wiring installation at which current is taken to supply utilization equipment. What this means is that if a light switch and a fixture outlet were on the same 2-wire branch circuit they would be subtracted from the maximum count of 12 receptacle outlets on the circuit which would leave 10. If the light fixture draws 3 amps plus the switch outlet, then the total circuit outlet count would be reduced to 8 receptacle outlets (12 -- 3 -- 1 = 8). On a standard specification home most electricians will wire one circuit per room, the outlet count usually never reaches the maximum of 12 outlets.
ten lights per curcuitCircuit loadingIn Canada there shall be not more that 12 outlets on any 2 wire branch circuit. Such outlets shall be considered to be rated at not more that 1 amp per outlet. Where the connected load is known, the number of outlets may exceed 12 providing the load current does not exceed 80 % of the rating of the over current device protecting the circuit.
Depends on what the outlets are controlling, size of the wire, and size of the breaker.
Branch circuit loading In Canada the CEC states that there shall be not more than 12 outlets on any 2-wire branch circuit. These outlets shall be considered to be rated at not less than 1 amp per outletWhere the connected load is known, the number of outlets shall be permitted to exceed 12, provided that the load current does not exceed 80% of the rating of the over current device protecting the circuit. For example on a 15 amp breaker, 15 x 80% = 12 amps, hence the standard of 12 outlets on any 2-wire branch circuit.On a 20 amp breaker, 20 x 80% = 16 amps. So from a 20 amp breaker this allows 16 outlets on a 2-wire branch circuit as long as the outlets are not considered to be rated at less than 1 amp per outlet.The definition of an outlet is a point in the wiring installation at which current is taken to supply utilisation equipment. What this means is that if a light switch and a fixture outlet were on the same 2-wire branch circuit they would be subtracted from the maximum count of 12 receptacle outlets on the circuit which would leave 10.If the light fixture draws 3 amps plus the switch outlet, then the total circuit outlet count would be reduced to 8 receptacle outlets (12 – 3 – 1 = 8).On a standard specification home most electricians will wire one circuit per room, the outlet count usually never reaches the maximum of 12 outlets.
Depends on the breaker. If the load at the outlets is unknown then the standard rules of 80% apply. You can only load a circuit 80% of it's maximum value. For instance, if you're connecting your GFCI outlets to a 15 amp breaker you can only have a maximum of 12 outlets. If it's a 20 Amp breaker then you're allowed up to 16 outlets and so on. In the US, you are limited to 13 receptacles on a 20 amp circuit and 10 receptacles on a 15 amp circuit in commercial or industrial installations. Any or all of these can be gfci-protected. You can install one gfci, the first one from the panel, and protect any or all the others from that one.
No, the six outlets are not amperage rated to be connected to a 20 amp circuit. A normal 15 amp receptacle can not be protected by a 20 amp breaker. Change the 20 amp breaker to a 15 amp breaker. This combination will pass code regulations. =============== In the United States, in a home, you can connect two hard-wired (not cord and plug connected) fans and six receptacles (outlets) to a single 20 amp circuit provided the 2 fans do not draw more than 10 amps together. If they are cord and plug connected, this limitation on the fans does not apply. In commercial and industrial installations, power to hard-wired equipment is provided on different circuits than receptacles.
10 for a 15 amp circuit