It is unusual to have multiple outlets on a 30 Amp service. If you do this you need outlets rated at 30 amps and 10 AWG wire.
Depends on the wire size used in the circuit. If you use AWG # 14 wire you must use a 15 amp breaker. If it is wired with AWG # 12 wire then you use a 20 amp breaker. If a AWG # 10 wire is used then a 30 amp breaker is required. The breaker protects the wiring from overheating so you must use the proper size breaker for the wire used.
well, the easy answer is, black wire to one pole of the breaker, white wire to the neutral bus with all the other white wires, bare wire to the ground bus with all the other bare (or green) wires. BUT the breaker must be 20 amps or less for residential outlets and you much match the wire size to the breaker, #14 for 15 amp breaker, #12 for a 20 amp breaker AND if there is only going to be one outlet, if it is a 20 amp circuit, the outlet has to be rated for 20 amps. Yes, but why would you want to? It is unclear to anybody else what you are doing and therefore a hazard. Do it right. Use a single pole breaker designed for 110V.
You will need to use #8 wire.
Look on the heater and see what amps it is pulling. That will determine the wire size and breaker size. It must be on a dedicated circuit. 15 amps = AWG # 14 wire with 15 amp breaker 20 amps = AWG # 12 wire with 20 amp breaker 30 amps = AWG # 10 wire with 30 amp breaker 40 amps = AWG # 8 wire with 40 amp breaker
No, electrical code typically requires that circuits be protected by a breaker that matches the wire size. A 30 amp breaker is typically used for circuits with larger wire sizes. For a 120V circuit, a 20 amp breaker is more suitable with appropriate wire size.
The size breaker you use is determined by the size wire used in the circuit. If you use AWG #12/2 wire then use a 20 amp breaker. If you use AWG # 14/2 then use a 15 amp breaker.
The appropriate wire size for a 25 amp breaker is typically 10 gauge wire.
The appropriate wire size for a 30 amp breaker is typically 10 gauge wire.
The recommended wire size for a 20 amp breaker is typically 12-gauge wire.
The recommended wire size for a 25 amp breaker is typically 10 gauge wire.
The recommended wire size for a 30 amp breaker is typically 10 gauge wire.
The recommended wire size for a 50 amp breaker is typically 6-gauge wire.
The recommended wire size for a 60 amp breaker is typically 6-gauge wire.
For a 30 amp breaker, you will need a wire that is at least 10 gauge in size.
The appropriate wire size for a 40 amp breaker is typically 8 AWG (American Wire Gauge).
The recommended wire size for a 40 amp breaker is typically 8 AWG (American Wire Gauge).
The recommended wire size for a 35 amp breaker is typically 8 AWG (American Wire Gauge) for copper wire.