legally you can use #10 awg wire but I would recommend using #8 awg wire. It would not get as hot as # 10 awg and could carry any overload you could have before the breaker would trip out...The breaker would trip very fast on any overload or shorted circuit before the amperage could affect either size wire but the #8 wire would just stay cooler. #10 AWG can only be fused at 30 amps per the "note" in national electric code (NEC) even though chart shows its ampacity is greater. Therefore, a load of 38 needs the larger wire. In addition if the furnance contains a motor load (usually it does) the motor part must have an extra 25% capacity added to the wire ampacity. So your 38 amp load may actually need wire sized to 40+ amps depending on the motor load. In addition if the ambient temperature of the room is high (like a boiler room) an additional factor probably need to be added. Refer to the charts in NEC
that would depend on the size of the blast furnace.
For a device operating on 240 VAC pulling 22 amps, you should use a wire that is at least 12-gauge in size to ensure it can safely handle the current without overheating. It's always a good idea to consult with a licensed electrician to determine the appropriate wire size and type for your specific application.
A #10 copper conductor with an insulation factor of 90 degrees C is rated at 30 amps.
The size of the breaker for a furnace will depend on the specific requirements of the furnace unit. It is recommended to check the furnace's user manual or consult with a qualified electrician to determine the correct breaker size for your particular furnace model. Using the wrong size breaker can be a safety hazard.
Add 25% so it comes to 42 amps
that would depend on the size of the blast furnace.
Number 8. Rated for 40 amps
#8 copper
AWG #3 copper.
For a device operating on 240 VAC pulling 22 amps, you should use a wire that is at least 12-gauge in size to ensure it can safely handle the current without overheating. It's always a good idea to consult with a licensed electrician to determine the appropriate wire size and type for your specific application.
A #10 copper conductor with an insulation factor of 90 degrees C is rated at 30 amps.
The size of the furnace depends on the square footage of the house you are heating.
1200 foot propane furnace what size do i need
The size of the breaker for a furnace will depend on the specific requirements of the furnace unit. It is recommended to check the furnace's user manual or consult with a qualified electrician to determine the correct breaker size for your particular furnace model. Using the wrong size breaker can be a safety hazard.
A parallel run of 750 MCM AWG conductors will handle 1000 amps. if we want 1000amps to flow, 250sqmm cable is enough.
To answer this question the pump voltage is needed.
Depending on size of Fridge. But AVERAGE is 12 volts for fridge, circuit necessity 15 amps 15 amps X 120 Volts=1800 watts minimum...I'm LEARNING myself