A #6 copper wire with an insulation factor of 75 or 90 degree C is rated at 65 amps.
18 amps.
A #8 copper wire with an insulation rated at 75 or 90 degrees C is rated at 45 amps.
A 400 MCM copper conductor will limit the voltage drop to 3% or less when supplying 100 amps for 700 feet on a 240 volt system. This size will allow the conductor to be loaded to 80 amps. 100 x 80% = 80 amps. Conductors are only allowed to be loaded to 80% or their rated capacity. If you need the full 100 amps then you would need to use a wire with a rating of 125 amps. 125 x 80% = 100 amps. A 600 MCM copper conductor will limit the voltage drop to 3% or less when supplying 125 amps for 700 feet on a 240 volt system.
Windows that can be opened.
CEC - any window that has the capacity to be opened.The exterior electrical service wires should be at least 3 feet away from any part of any window that is able to be opened.
150 amps
18 amps.
AWG # 6 copper
30 amps is how much a 10-2 wire will carry at 110 feet. 10 gauge wire is only good for thirty amps per the national electrical code. Using 80% of the breakers usage you will actually be getting only 24 amps.
Yes, a #10 wire will carry 30 amps for 30 feet. If the load is rated as continuous then the wire will have to be derated to 80% capacity which will leave you with 24 workable amps. If the load demands currents higher that 24 amps then you will have to go to the next wire size up which is a #8 which is rated at 45 amps.
A 3/0 copper conductor will limit the voltage drop to 3% or less when supplying 200 amps for 200 feet on a 240 volt system.
8 AWG copper is rated for 40 amps. Over 150 ft, at maximum current, the voltage drop would be about 3.76 volts. Using 6 AWG would have a voltage drop of 2.36 volts with the same 40 amps.
A #4 copper conductor will limit the voltage drop to 3% or less when supplying 25 amps for 400 feet on a 120 volt system.
A #8 copper wire with an insulation rated at 75 or 90 degrees C is rated at 45 amps.
A 400 MCM copper conductor will limit the voltage drop to 3% or less when supplying 100 amps for 700 feet on a 240 volt system. This size will allow the conductor to be loaded to 80 amps. 100 x 80% = 80 amps. Conductors are only allowed to be loaded to 80% or their rated capacity. If you need the full 100 amps then you would need to use a wire with a rating of 125 amps. 125 x 80% = 100 amps. A 600 MCM copper conductor will limit the voltage drop to 3% or less when supplying 125 amps for 700 feet on a 240 volt system.
10 guage
A 3/0 aluminum conductor will limit the voltage drop to 3% or less when supplying 150 amps for 150 feet on a 240 volt system. This size will allow the conductor to be loaded to 120 amps. 150 x 80% = 120 Conductors are only allowed to be loaded to 80% or their rated capacity. If you need the full 150 amps then you would need to use a wire with a rating of 190 amps. 190 x 80% = 152 amps A 4/0 aluminum conductor will limit the voltage drop to 3% or less when supplying 190 amps for 150 feet on a 240 volt system.