For a 400 amp service, you would typically use 500 kcmil copper wire or 600 kcmil aluminum wire for the main service conductors. It's important to consult with a licensed electrician and check local electrical codes to ensure the correct wire size is used for your specific installation.
For a 400 amp service, it is recommended to use 3-inch conduit to allow for the appropriate wire size and future updates. This will provide enough space for the conductors to be pulled through without causing damage. It is important to verify the specific requirements with local building codes and regulations.
We recommend using a #6 copper wire for the connection between the breaker box and the earth ground rod. This size wire is commonly used for grounding purposes and is sufficient for carrying the electrical current safely to the ground rod. Be sure to consult with a qualified electrician to ensure the proper materials and installation for your specific situation.
Assuming you are working with 240v, you need 4/0 copper conductors.
A 400 watt heater can safely be used on a 15 amp circuit. The size breaker needed for a circuit is determined by the size of the wiring in that circuit. AWG #14 wire requires a 15 amp breaker. AWG # 12 wire requires a 20 amp breaker.
For a distribution panel rated at 400 amps parallel runs of 3/0 conductors will do the job.
Depends upon the voltage. The formula for amperage or (wire size) is Watts / Voltage. If the voltage is 220 volts, then the amperage would be over 400 amps. This would require a large wire size to run it. If it were 440 volts, the amperage would be 1/2 or 200 amps. That would require a smaller wire size. As the voltage goes up, the amperage goes down. At a thousand volts, the amperage would only be 90 amps. A wire gauge or size of a #2 would carry 90 amps for small distances.
For a 400 amp service, you would typically use 500 kcmil copper wire or 600 kcmil aluminum wire for the main service conductors. It's important to consult with a licensed electrician and check local electrical codes to ensure the correct wire size is used for your specific installation.
Use AWG # 4 copper and you will have a 2.6% voltage drop which is acceptible.
For a 400 amp service, it is recommended to use 3-inch conduit to allow for the appropriate wire size and future updates. This will provide enough space for the conductors to be pulled through without causing damage. It is important to verify the specific requirements with local building codes and regulations.
To answer this question a voltage needs to be stated. The formula needed to find the amperage is I = W/E. Amps = Watts/Voltage. Once the amperage is found, the proper size conductor to handle that current can be established. Without knowing the amperage on 400 watts a good guess would be a #14 wire. This wire size is good up to 1440 watts at 120 volts.
3r x 300sq.mm Al. ar UG cable <<>> Wiring is sized by the amperage that is used by the load. The formula for amps is I = W/E. Amps = Watts (or VA)/Volts. As you can see an answer can not be given unless a voltage is stated. The lower the primary voltage the larger the amperage will be and likewise the larger the wire size will be.
We recommend using a #6 copper wire for the connection between the breaker box and the earth ground rod. This size wire is commonly used for grounding purposes and is sufficient for carrying the electrical current safely to the ground rod. Be sure to consult with a qualified electrician to ensure the proper materials and installation for your specific situation.
At least 50mm but with all the de-rating factors it might be 70mm that's if its 2 cable single phase non armoured clipped direct. Check out the tables dopey!!!! FYI 50 mm = 2 inches, 70 mm = 2.75 inches these are not wire sizes, sound more like cable outside diameters. Correct answer The wire size is dependant on the insulation factor on the wire. A few common insulations and corresponding wire sizes for 150 amps are - Size 0 R90 good for 155 amps, also with insulations of RW 75, TWH, TW75, good for 150 amps. Size 000 TW good for 165 amps.
A 228 sq mm conductor equates to 450 MCM. A conductor of 450 MCM is not a standard AWG wire size. A standard 400 MCM will carry 380 amps. A standard 500 MCM will carry 430 amps. Difference between 400 and 500 MCM amperage's is 50 amps. Transposing between the two amperage's of 50 amps will be 380 + 25 = 405 or 430 - 25 = 405 amps. This is a very rough calculated answer for the question.
A 500 MCM wire with an insulation factor of 90 degrees C is rated at 430. Most 400 amp services will use parallel wires on each leg to feed the circuit. A 3/0 wire with an insulation factor of 75 and 90 degrees C is rated at 200 and 225 amps respectively. The insulation rating of these conductors will be 600 volts.
Assuming you are working with 240v, you need 4/0 copper conductors.