This is a voltage drop question. To answer the question about distance a voltage must be stated. That said a #10 copper conductor with an insulation factor of 75 or 90 degrees C are both rated at 30 amps.
A #16 copper conductor is not a wiring size that is used in homes. This is because the smallest breaker for residential use is rated for 15 amps. A #16 copper conductor is only rated at 13 amps. For a load of 13 amps over 100 feet a #12 copper would be required.
Yes, 14-2 wire is rated to carry up to 15 amps of current. However, the length of the wire, in this case 80ft, can increase the resistance of the wire, potentially causing voltage drop. It's recommended to consult with an electrician to ensure the wire size and length are suitable for the intended application.
The number of automotive amps a 30-foot strand of copper wire can carry depends on the gauge (thickness) of the wire. For example, a 30-foot strand of 10-gauge copper wire can typically carry up to 40-50 amps for automotive use, while a 30-foot strand of 12-gauge wire might be limited to around 25-30 amps. It's important to consult wire ampacity tables and consider factors like temperature and voltage drop to ensure safe and effective performance.
The wire size typically used for a 60 amp low voltage cable is AWG 6 or AWG 8 depending on the specific application and voltage requirements. It's important to consult the manufacturer's specifications for the appropriate wire size for your particular setup.
To answer this question a voltage must be given.
Depends upon the voltage. The formula for amperage or (wire size) is Watts / Voltage. If the voltage is 220 volts, then the amperage would be over 400 amps. This would require a large wire size to run it. If it were 440 volts, the amperage would be 1/2 or 200 amps. That would require a smaller wire size. As the voltage goes up, the amperage goes down. At a thousand volts, the amperage would only be 90 amps. A wire gauge or size of a #2 would carry 90 amps for small distances.
Wire is sized by the amperage that it will carry. 5 kW is 5000 watts. The equation to find watts is W = Amps x Volts. The equation to find amps is Amps = Watts/Volts. As you can see a voltage is needed to calculate the amperage. Once the amperage is stated, the wire size can be given for that particular amperage.
A # 14 copper conductor will be fine to carry 8 amps at 120 volts. This size conductor is rated at 15 amps.
14
This is a voltage drop question. To answer the question about distance a voltage must be stated. That said a #10 copper conductor with an insulation factor of 75 or 90 degrees C are both rated at 30 amps.
To answer this question a voltage and amperage must be stated. W = Amps x Volts.
The V stands for volts and A is amps. If for example you have a 12kVA device and are running off a voltage of 120 volts then Amps = 12000/120 = 100. You then use the calculated amps in a wire size table to get the correct size.
A #16 copper conductor is not a wiring size that is used in homes. This is because the smallest breaker for residential use is rated for 15 amps. A #16 copper conductor is only rated at 13 amps. For a load of 13 amps over 100 feet a #12 copper would be required.
Couple of things wrong here. 30 isn't a wire size. If you mean a wire that can carry 30 amps that would be # 10. Now it depends on how many # 10 wires you want to put into a conduit that governs the size of the conduit.
Because of voltage drop, 4 awg copper would be recommended for that distance run. <<>> A #1 copper conductor will limit the voltage drop to 3% or less when supplying 50 amps for 200 feet on a 110 volt system.
AWG # 6 copper