answersLogoWhite

0


Best Answer

All North American utility suppliers are set up for 60 Hz. As such, all breakers are designed for 60 Hz operation.

Although European electricity is 50 Hz, North American breakers would no doubt function well.

It is highly recommended that you employ the services of a qualified electrician for installation or modification of any electrical service.

User Avatar

Wiki User

13y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: How do you get the hertz of a circuit breaker 200 amps?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

What is the rating of the main circuit breaker of the 60kw power distribution panel?

200 amps


What is the amperage rating of the mission essential power MEP circuit breaker of the secondary distribution center?

200 amps


Can you install a 2 20 breaker into a breaker box that has space but all other breakers add up to more amps than the 200 amp main breaker?

Yes. You'll seldom run every circuit to full capacity. The main breaker will trip if all the individual circuits exceed the 200 amp rating of the main breaker.


How many breaker amps will a 200 amp service with no main breaker support?

Check the nameplate on the service panel. There it will tell you what the buss capacity is. On a 200 amp service nothing in the wiring configuration is allowed to be less than that the service rating. In the market there are 200 amp 42 circuit distribution panels.


Is it safe to have 200 plus amps in breakers inside than 90 amps on the main service breaker outside?

I am assuming by your description that the panel is protected by a 90 amp breaker and the breakers in the panel when added up is 200. This is okay as long as your 90 amp breaker trips on a regular basis. It is typical for the breakers to add up to more than the main breaker under the assumption that you would rarely be running each circuit at its maximum capacity.


Cost to install 1200 Amps Circuit Breaker?

1200 Amps is a huge breaker. Typical houses might have between 100 and 200 Amp service. Since this would have to be a very unique installation you would have to provide a lot more information before cost could be computed. You also have to indicate who is supplying the breaker which would be a significant cost on its own.


If you're installing a circuit that will contain receptacles in an industrial area and the first receptacle is more than 50 feet (15.24 meters) from the load center you should?

Connect the circuit to the appropriate size circuit breaker to meet the required amperage of the circuit. Turn the breaker on and use the circuit. Unless the circuit is of a very high ampacity, plus 200 amps, don't worry about voltage drop over 50 feet.


How much you can use in 200A breaker?

200. Although you cannot exceed current ratings on any branch circuit without tripping that circuit. You need to make sure that you do not exceed 160 continuous load amps to meet NEC requirements of not overloading a breaker to more than 80% under continuous load.


Can you hook up 200 amp dervice to a 125 amp service panel?

No. If device draws 200 amps breaker will trip.


What is the maximum amps each phase conductor carries on 200 amp residential service?

If the mains is a 200 amp two pole breaker each leg can carry up to 200 amps in relationship to the common neutral of the service.


What size breaker and wire for barn lighing 10 x 60W bulbs and outlets which are 200 feet from main box?

For the lighting load the amperage is A = W/V = 600/120 = 5 amps. As for what will be plugged into the receptacles will be a guess for the calculations. I will give you a full 15 amps for receptacle loads at 120 volts. Total amperage is 20 amps. The breaker for this circuit will be a 20 amp breaker but there may be a problem getting the #6 wire under the breakers terminal connection points. If this is the case use a #6 lug to connect to the breaker and connect the wire into the lug. A #6 copper conductor will limit the voltage drop to 3% or less when supplying 20 amps for 200 feet on a 120 volt system.


How much loss from power pole to 200 amp breaker box then off 400 feet then split at a pump house then another 30 feet to a 100 amp breaker box?

For an accurate calculation it will be necessary to know what the size of breaker exists in the pump house and what size conductors are used. Power loss is measured using actual amps required, not size of the circuit involved. But the size of circuit (breaker size) can be used. Voltage must also be known.