530 amps in average conditions, more in cold weather. <<>> The closest conversion will be; 405 mm2 is equal to 800 MCM AWG. A 800 MCM aluminium conductor with an insulation factor of 90 degrees C is rated at 445 amps.
300 Amps if used for service entrance conductors. Table 310.15
There are different combination to obtain a current capacity of 1250 amps. A parallel run of #1250 MCM wires. A triple run of #600 MCM wire. The most flexible run would be with a quad run of #350 MCM wire.
500mcm 37 strand copper wire = 1.544lbs/ft.
Allowable ampacities for a single 350 MCM aluminium conductor with an insulation factor of 90 degrees C is rated at 445 amps.Allowable ampacities for no more that three 700 MCM aluminium conductors in a conduit with an insulation factor of 90 degrees C are rated at 425 amps.
A 228 sq mm conductor equates to 450 MCM. A conductor of 450 MCM is not a standard AWG wire size. A standard 400 MCM will carry 380 amps. A standard 500 MCM will carry 430 amps. Difference between 400 and 500 MCM amperage's is 50 amps. Transposing between the two amperage's of 50 amps will be 380 + 25 = 405 or 430 - 25 = 405 amps. This is a very rough calculated answer for the question.
530 amps in average conditions, more in cold weather. <<>> The closest conversion will be; 405 mm2 is equal to 800 MCM AWG. A 800 MCM aluminium conductor with an insulation factor of 90 degrees C is rated at 445 amps.
300 Amps if used for service entrance conductors. Table 310.15
For a 400 amp service, you would typically use 500 kcmil copper wire or 600 kcmil aluminum wire for the main service conductors. It's important to consult with a licensed electrician and check local electrical codes to ensure the correct wire size is used for your specific installation.
2/0 if copper is used; 4/0 if aluminum is used. The neutral and ground are usually smaller. 2/0 is only rated for 185 amps. 3/0 copper is rated for 210 amps, 250 MCM is rated at 215 amps if aluminum is used.
It depends on a lot of factors. Generally speaking, if the insulation is THHN then the rating is 350 amps. If the insulation is THWN then the rating is 310 amps. The ampere rating for wire depends on the temperature of the environment it will be used in, the insulation rating and the number of circuits installed in a conduit. There are also other factors to consider... like voltage drop in long runs.
475 amps, per NEC 310-16. Note that this is a maximum; there are many reasons to derate the current carrying capacity of the wire.
There are different combination to obtain a current capacity of 1250 amps. A parallel run of #1250 MCM wires. A triple run of #600 MCM wire. The most flexible run would be with a quad run of #350 MCM wire.
The amp rating of a 500 MCM (thousand circular mil) cable can vary depending on the insulation type and installation conditions. Generally, a rough estimate for a 500 MCM cable with THHN insulation in a typical installation would be around 380-400 amps. However, it is recommended to consult the manufacturer's specifications or a qualified electrician to determine the exact ampacity for a specific application.
generally size 500 MCM, but there can be factors which would require up-sizing, such as high ambient temperature long run causing excessive voltage drop multiple circuits in same raceway
A 1000 MCM copper conductor will limit the voltage drop to 3% or less when supplying 150 amps for 400 feet on a 120 volt system.
The UK wire tables for 1.0 mm2 three-core domestic cable (live/neutral/earth) specify a limit of 10 amps.