There are different combination to obtain a current capacity of 1250 amps. A parallel run of #1250 MCM wires. A triple run of #600 MCM wire. The most flexible run would be with a quad run of #350 MCM wire.
A #1 copper conductor will limit the voltage drop to 3% or less when supplying 95 amps for 200 feet on a 208 volt system. This size will allow the conductor to be loaded to 76 amps. 95 x 80% = 76 amps Conductors are only allowed to be loaded to 80% or their rated capacity. If you need the full 95 amps then you would need to use a wire with a rating of 120 amps. 120 x 80% = 96 amps. A 1/0 copper conductor will limit the voltage drop to 3% or less when supplying 120 amps for 200 feet on a 208 volt system.
For single phase 30 amps at 120 volts you would need a #8 copper wire with an insulation rating of 90 degrees C.
8 is the size of wire to use for grounding a 100 Amp panel. Green is color used for grounding8 is code.A #3 copper wire with an insulation rating of 75 or 90 degrees C is rated at 100 and 110 amps consecutively.
Over the short distance of 25 feet no voltage drop calculations are needed to be made. A #10 copper conductor with an insulation rating of 60, 75 or 90 degrees C is rated at 30 amps respectively. 30 x 80% = 24 amps. If the load is under 24 amps then this size is the one to use. If the load current is greater than 24 amps then use a conductor one size larger. That would be a #8 which is rated at 45 amps x 80% for maximum wire loading = 36 amps.
I would recommend 1/0 just to be sure you have very little line loss. <<>> It depends on whether the 100 amp panel is rated at 100% or 80% loading. If the panel is only rated for 100% loading, meaning that a full 100 amps can be drawn from it, the wire size will be #2 copper conductor which is rated at 130 amps. The feeder can only be loaded to 80 present so will have a working amperage of 130 x .8 = 104 amps. If the panel is only rated at 80 percent loading then a #3 copper conductor can be used. A #3 copper conductor with an insulation factor of 90 degrees C is rated at 115 amps. 115 x .8 = 92 amps.
A #10 copper wire with an insulation factor of 90 degrees C is rated at 30 amps. If you need the full 30 amps for the load use a #8 copper wire. Loaded to 80% of rating will give you 32 usable amps.
The wire size for 600 amps on a single wire 1250 MCM. A 1250 MCM copper conductor is rated for 645 amps with an insulation rating of 90 degrees C. This size of wire is too large to handle easily when it comes to the terminations. A service requiring 600 amps is usually paralleled or tripled which reduces the wire size which makes the wire much easier to handle. For a parallel service two 350 MCM cables are used and for a triple parallel run three 2/0 conductors are used. These conductors all have an insulation rating of 90 degrees C.
A #1 copper conductor will limit the voltage drop to 3% or less when supplying 95 amps for 200 feet on a 208 volt system. This size will allow the conductor to be loaded to 76 amps. 95 x 80% = 76 amps Conductors are only allowed to be loaded to 80% or their rated capacity. If you need the full 95 amps then you would need to use a wire with a rating of 120 amps. 120 x 80% = 96 amps. A 1/0 copper conductor will limit the voltage drop to 3% or less when supplying 120 amps for 200 feet on a 208 volt system.
For single phase 30 amps at 120 volts you would need a #8 copper wire with an insulation rating of 90 degrees C.
The heater should have a wattage rating (very few list amps). Calculate the amps using the wattage and voltage. Amps = Watts/Volts(480).
8 is the size of wire to use for grounding a 100 Amp panel. Green is color used for grounding8 is code.A #3 copper wire with an insulation rating of 75 or 90 degrees C is rated at 100 and 110 amps consecutively.
10 gauge
This is a voltage drop question. A voltage at 30 amps needs to be stated to answer the question.
A 3/0 copper conductor with an insulation rating of 90 degrees C is rated at 225 amps.
You would need to use a #12 copper conductor to continuously draw 14 amps at 120 volts.
A 3/0 copper conductor with an insulation rating of 75 or 90 degrees C is rated at 200 and 210 amps respectively. A 3/0 copper conductor will limit the voltage drop to 2% or less when supplying 200 amps for 80 feet on a 240 volt system.
Use AWG # 3 copper.