Assuming the can lights is all that will be on this 15 amp 120 volt circuit and each one has no more than a 75 watt bulb installed you can install up to 19. This is determined by multiplying the amps x the voltage to get the wattage. 15 x 120 = 1800. Then multiply the 1800 x 80% and you get 1440 which places an 80% load on the circuit which is all you safely want. You then divide the 1440 by 75 which is the wattage of each bulb and you get 19.2. You could add more if you use fluorescent bulbs but someone could come along later and install incandescent bulbs and overload the circuit. So stick with no more that 19 to be safe. Remember this is a 15 amp ciruit so you must use AWG # 14 wire and not #12. If you use AWG #12 and a 20 amp breaker you can have 25 can lights with 75 watt bulbs on the circuit.
Wiki User
∙ 10y agoA 30 amp breaker is usually used for a dedicated 30 amp device. Ordinary 15 amp receptacles can not be connected to a breaker of higher trip capacity than the rating of the receptacle. The wire size for a 30 amp breaker is #10 AWG.
No, you cannot use one in place of the other.
If you are asking, can three separate 240 volt circuits be run off of one 50 amp breaker then the answer is no. Not without knowing what the loading of the three circuits are and whether all three circuits could be on at the same time.
All depends on how big your main breaker is and what size wire you are using,one 20 amp outlet needs #12 wire not more than 50feet away from main breaker
If there is a possibility of both operating simultaneously, then a 100 amp breaker (actually 80 amp if you can find one), and appropriate wiring would be required. Even if they were not expected to operate simultaneously, it would be prudent to wire as if they were.
Code only allows one wire to be connected to a single pole breaker. Any additional circuitry has to be done in a junction box downstream from the breaker.
It is not recommended to replace a 20 amp circuit breaker with a 25 amp one. Circuit breakers are designed to protect the wiring and equipment from overheating and potential fires. Using a breaker with a higher rating than the wiring can handle increases the risk of overheating and could lead to a fire hazard. It is important to match the circuit breaker size to the wiring and equipment it is protecting.
No, you should not replace a 30 amp fuse with a 40 amp circuit breaker as it would exceed the designed electrical capacity for the cooker. It's important to match the electrical protection device (fuse or circuit breaker) with the current rating of the appliance to prevent overheating and potential fire hazards.
No, you cannot interchange a 250v 15 amp breaker with a 115v 15 amp breaker. Breakers are voltage-specific devices, and using the wrong voltage breaker can be a safety hazard and can damage your electrical system. It is essential to use the correct voltage and amperage ratings for your electrical circuit.
Multiple wires can be connected to one breaker but the one breaker IS a circuit. As long as the load is not more than 80% of the breaker capacity (example: a 20 amp breaker can only have 16 amps or 1920 watts at 120 volts) then by code as long as the load is not a specialty outlet of some sort, you can have as many outlets you want.
On a 15 amp household breaker there is no terminal on the in feed of the breaker. The breaker either plugs into the distribution panel's bus bar or it bolts to the distribution's bus bars. The feed conductor connects to the load side of the breaker at its terminal lug.
No. If your AC is currently running on a 30 amp 2 pole breaker, then it is a 220 volt unit. You cannot substitute one 60 amp single pole breaker as you'll only be supplying 110 volts and the AC unit won't work. In fact you could damage it.
A 30 amp breaker is usually used for a dedicated 30 amp device. Ordinary 15 amp receptacles can not be connected to a breaker of higher trip capacity than the rating of the receptacle. The wire size for a 30 amp breaker is #10 AWG.
The load exceeds the limit of the breaker or fuse. For example a 20 amp breaker on a 120 volt circuit will handle 2400 watts. Exceed that wattage and the breaker will trip or the fuse will blow.
For a main breaker to trip under these circumstances the rest of the panel is becoming close to its load rating. When the 20 amps breaker trips the rest of the panel is close to or over 30 amps, the 20 amp breaker takes it over the top. What trips a HWT breaker is usually a faulty heating element. It could be the top one or the bottom one.
SeeIf_a_100A_breaker_panel_has_five_15A_breakers_and_four_20A_breakers_could_this_overload_the_panel
No, a Meter Main Combo typically includes the main breaker as part of its design, so you would not need an additional main breaker in the panel. The main breaker in the Meter Main Combo serves as the disconnect for the panel.