answersLogoWhite

0

On large service entrance services the neutral can be reduced. The amperage of the service and the voltage of the service and the insulation factor of the 500 MCM conductors need to be stated to answer this question correctly.

User Avatar

Wiki User

12y ago

What else can I help you with?

Continue Learning about Electrical Engineering

If service is fed with service entrance conductors of 500 MCM THHN copper and fused at 400 amps What would be the minimum size of a copper grounding electrode conductor?

For a service rated at 400 amps using 500 MCM THHN copper conductors, the minimum size for a copper grounding electrode conductor (GEC) can be determined using the National Electrical Code (NEC) guidelines. According to NEC Table 250.66, for a service of 400 amps, the minimum size for a copper GEC is 4 AWG. However, if the GEC is connected to a ground rod, it must be a minimum of 6 AWG copper.


Can triplex be run in underground conduit?

YesIn Canada the answer is no. Triplex is an aerial rated set of conductors that are used to bring the voltage from the utilities pole to the service drop at the home. Triplex consists of two ungrounded conductors wrapped around a neutral steel supported conductor. These conductors can be used on higher current capacities due to the direct cooling of the conductors by the surrounding air. This is why you will see a service drop of number 6 conductors supplying a 100 amp service. For a three phase four wire system quadplex is used to make three phase connections to commercial and industrial services.


What is the cable between the service panel and electric meter called?

Whether you have an overhead or underground feed, that section of the installation is referred to as Service Entrance Conductors. On an overhead installation, it includes the conductors on BOTH sides of the meter, from the service drop conductors (attached at the service head) to the service equipment LINE terminals. On an underground installation, it refers only to the conductors between the meter's LOAD side and the service equipment LINE terminals. The conductors on the LINE side of the meter come from a distribution transformer and are unbroken between the transformer and your meter.


What wire size is needed for 1800 amp service?

There is no one wire that is rated for 1800 amps. The service will have to be a quad parallel of the conductors. A 600 MCM conductor with an insulation factor of 90 degrees C is rated at 475 amps. This conductor paralleled into four equal lengths will give an ampacity of 1900 amps for each leg of the service.


What size ground do i use for a 600 amp service 350 kcmil conductors?

For a 600 amp service using 350 kcmil conductors, the appropriate ground size typically follows the National Electrical Code (NEC) guidelines. For a service of this size, a minimum of 2/0 AWG copper or 4/0 AWG aluminum is generally recommended for the equipment grounding conductor. However, always consult the latest NEC code and local regulations, as requirements may vary. Additionally, consider factors like the length of the run and specific installation conditions.

Related Questions

How do you size the neutral in a 240 volt system?

On a 120/240 volt distribution the neutral is sized along with the supply conductors. The sizing is based on the amperage of the service distribution.


What size service conductors for a 225 amp 3 phase service?

For a 225 amp 3-phase service, typically you would use 3 sets of 3/0 AWG copper conductors or 250 kcmil aluminum conductors for the service entrance conductors. Make sure to consult the National Electrical Code (NEC) and local regulations for specific requirements.


800 amp service using parallel sets of 500 cu what size grounding electrode conductor?

For an 800 amp service with parallel sets of 500 kcmil copper conductors, the grounding electrode conductor size should be based on the largest conductor in the parallel set. The grounding electrode conductor size should be sized based on Table 250.66 in the NEC, which recommends a minimum size of 3/0 AWG copper for 1/0 AWG or larger service-entrance conductors.


What are all of the conductors between the service equipment and the final branch circuit?

The conductors between the service equipment and the final branch circuit include service conductors, feeder conductors, and branch circuit conductors. Service conductors connect the utility service to the service equipment. Feeder conductors distribute power from the service equipment to the panelboard or distribution board. Branch circuit conductors then carry power from the panelboard to individual outlets, fixtures, and appliances.


What size service ground is needed for a 350 parallel service?

From the question it is hard to establish whether the service size is 350 amps or the service conductors are 350 MCM in parallel. If the service is 350 amps, the grounding conductor is #3 bare copper wire. Parallel 350 MCM conductors will allow for a 600 amp service. The grounding conductor for a 600 amp service is a #1 bare copper wire.


What is The minimum distance that consumer's service conductors should extend beyond the service head is?

The minimum distance that a consumer's service conductors should extend beyond the service head is typically 3 feet. This requirement ensures adequate clearance for safe connections and maintenance. However, local codes and regulations may vary, so it's essential to consult the applicable electrical code in your area for specific requirements.


If service is fed with service entrance conductors of 500 MCM THHN copper and fused at 400 amps What would be the minimum size of a copper grounding electrode conductor?

For a service rated at 400 amps using 500 MCM THHN copper conductors, the minimum size for a copper grounding electrode conductor (GEC) can be determined using the National Electrical Code (NEC) guidelines. According to NEC Table 250.66, for a service of 400 amps, the minimum size for a copper GEC is 4 AWG. However, if the GEC is connected to a ground rod, it must be a minimum of 6 AWG copper.


What is single phase 480?

The utility company can provide a 480 volt, single phase service from a single phase transformer, usually with a three wire service. 480 volts is measured between the two line conductors, and 240 volts is measured between either line conductor and the common neutral conductor. The voltage of the line conductors are at 180 degrees with respect to the neutral conductor.


What size conductors are needed for 800 amp service?

For an 800 amp service, typically 4/0 AWG conductors are needed for the hot conductors and 2/0 AWG for the neutral conductor in a 3-phase system. However, it is recommended to consult with a qualified electrician to determine the exact size based on the specific installation requirements and local electrical codes.


What does SN stand for in an old style fuse panel it is referring to the neutral bars?

The term SN refers to a panel or disconnect switch that has solid neutral bar installed. It is a small bar that allows the service conductors to be bonded to the enclosure at that point.


Can triplex be run in underground conduit?

YesIn Canada the answer is no. Triplex is an aerial rated set of conductors that are used to bring the voltage from the utilities pole to the service drop at the home. Triplex consists of two ungrounded conductors wrapped around a neutral steel supported conductor. These conductors can be used on higher current capacities due to the direct cooling of the conductors by the surrounding air. This is why you will see a service drop of number 6 conductors supplying a 100 amp service. For a three phase four wire system quadplex is used to make three phase connections to commercial and industrial services.


What size service conductors do you need for a single phase 600 amp commercial panel?

The size of wire for service entrance conductors for a 400 amp 3 phase service could be 500 MCM copper. This is very large size wire and difficult to bend and shape, to connect to terminals in the main disconnect and distribution panel. This problem is solved by using parallel conductors or on higher ampacities triple conductors. Using parallel conductors the wire size would be three ought (3/0) copper.