This answer is taken from the CEC. Table 17 states minimum size of grounding conductors. For a service conductor drawing 400 amps a #3 copper grounding conductor is needed. Also see rules 10-206, 10-700 and 10-812 if you have access to the code book.

User Avatar

Wiki User

13y ago

What else can I help you with?

Related Questions

What is the recommended ground wire size for a 100 amp sub panel installation?

The recommended ground wire size for a 100 amp sub panel installation is typically 8 copper wire.


What is the largest size ground wire that can be used for a panel?

Use #10 copper.


What size ground wire should I use for a 50 amp hot tub panel?

# 10 bare copper.


Ground wire size for 200?

The size of the ground wire for a circuit is typically based on the size of the circuit breaker protecting that circuit. For a 200 amp circuit breaker, the recommended ground wire size is 4/0 AWG (American Wire Gauge) copper wire. This wire size helps ensure that the ground wire can safely carry any fault currents that may occur in the electrical system.


What size ground wire needed for a 200amp service panel in new jersey?

#6 bare copper wire.


How do you know what wire is ground on 200 amp service?

On a 200 amp or any size service the ground wire is easily identified. Look in the distribution panel for the neutral bus bar. This is where the service neutral (white wire) is connected to the distribution panel. There you will see a bare copper wire connected to the same neutral bar. This is the ground wire that is connected to the ground rods out side of the house.


What is the recommended ground wire size according to the NEC Ground Wire Size Chart?

The recommended ground wire size according to the NEC Ground Wire Size Chart is based on the amperage of the circuit.


What size of ground wire for a bank of 3 one 100 amp panels?

#8 would be fine if you ground each panel separately to the ground rod


What information does the sub panel wire size chart provide for determining the appropriate wire size for a sub panel installation?

The sub panel wire size chart provides information on the recommended wire size based on the amperage of the sub panel, the distance the wire needs to run, and the type of wire insulation. This helps determine the appropriate wire size for a sub panel installation to ensure safety and efficiency.


How do you select earthing conductor size of any motor panel etc?

The ground wire size is determined from the current carrying capacity of the motor feeders.


In a typical electrical panel installation the main ground wire is connected directly from a ground rod driven into the ground to the?

The ground wire should come from the ground rod and to the main electrical panel grounding terminal.


What size wire should be used for a sub panel installation?

The size of wire needed for a sub panel installation depends on the amperage of the sub panel. It is recommended to consult with a licensed electrician to determine the appropriate wire size for your specific installation.