It all depends on the voltage and wattage of the dryer: maybe you only need 30 amp breakers with 10/3 wire, or maybe you need thicker wire and bigger breakers?
The rating plate on the dryer should tell you want power it takes and, if you are going to do this job safely and correctly, you should first of all be able work out the current or amperage from an appliance's power and the voltage.
<><><>
As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.
Before you do any work yourself,
on electrical circuits, equipment or appliances,
always use a test meter to ensure the circuit is, in fact, de-energized.
IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS.
Yes as long as you change the 50 amp breaker to a 15 amp breaker. You will be hard pressed to get the 50 amp #6 wire under the terminals of the 15 amp receptacle.
No, it is not safe to use a #8 conductor on a 50 amp breaker. A #8 conductor is only rated at 45 amps capacity. By connecting it to a 50 amp breaker, which would trip at 50 amps on an overload, would overload the conductor by an extra 5 amps. This would be a conflict against the electrical code.
Both a 45 amp and 50 amp breaker would require 6 AWG wire. So if you have 6 AWG wire and any devices like an outlet are rated at 50 amps or greater you are okay.
Not legally because the rating of the 30 amp receptacle would have a 50 amp breaker ahead of it. If you reduced the feed breaker to 30 amps and still use the #6 wire, this would be within the electrical code rules.
A 30 amp breaker run 75 feet would require you use AWG #10 wire. But, an oven normally pulls more that 30 amps and I would not use #10 wire on a 30 amp breaker for an oven. Normally any newer oven is wired with AWG #6 gauge wire on a 50 amp circuit breaker so the breaker will not trip during heavy use of the oven. Some older ovens could use a #8 wire on a 40 amp breaker.
A 50 amp breaker is an overcurent device.
For a stove, use a 8 or 6 gauge wire with a 40 to 50 amp breaker. For a dryer, use a 10 or 8 gauge wire with a 30 amp breaker. For a hot water heater, use a 10 or 8 gauge wire with a 30 or 40 amp breaker. Be sure to consult local electrical codes and guidelines for specific requirements.
Theoretically yes if you remove the two pole 50 amp breaker and replace it with a 2 pole 15 amp breaker. This has to be done because the new receptacle is only rated at 15 amps and can not be protected by a breaker any larger than 15 amps.Physically this is not going to happen due to the fact that you will not be able to connect the existing #6 conductor, which fed the 50 amp dryer receptacle, under the terminals of the new 2 pole 15 amp breaker.
No, a double pole 50 amp breaker protects a 240 volt supply at 50 amps. The number that is on the handle of the breaker is the amperage that the breaker will trip at if an overload occurs on the circuit.
No .
For a 41 amp load, you would typically use a 50 amp circuit breaker. The general rule is to select a breaker size that is 125% of the continuous load amps or equal to the load amps if it is not a continuous load. In this case, 41 amps is considered a continuous load, so you would round up to the nearest available breaker size, which is 50 amps.
Yes, you can operate a 30 amp dryer on a 50 amp receptacle. The receptacle will be compatible with the lower amperage appliance, but it's always safer to use the correct amperage outlet for the appliance for optimal safety and performance.
Yes as long as you change the 50 amp breaker to a 15 amp breaker. You will be hard pressed to get the 50 amp #6 wire under the terminals of the 15 amp receptacle.
No, it is not safe to use a #8 conductor on a 50 amp breaker. A #8 conductor is only rated at 45 amps capacity. By connecting it to a 50 amp breaker, which would trip at 50 amps on an overload, would overload the conductor by an extra 5 amps. This would be a conflict against the electrical code.
Yes, a 100 amp main panel can have 2 separate 50 amp circuits protected by 50 amp breakers. This configuration allows for two separate circuits drawing up to 50 amps each from the main panel without overloading the panel's 100 amp capacity.
In North America this size breaker could be used on a welding machine. A range in the home would use a 40 amp two pole breaker.
Both a 45 amp and 50 amp breaker would require 6 AWG wire. So if you have 6 AWG wire and any devices like an outlet are rated at 50 amps or greater you are okay.