answersLogoWhite

0

What else can I help you with?

Continue Learning about Electrical Engineering

How many amps is 600 mcm good for?

The ampacity of 600 kcmil (mcm) copper wire varies depending on the application and installation conditions, such as whether it is in conduit or in free air. Generally, 600 kcmil copper wire can carry approximately 700 to 800 amps at a temperature rating of 75°C. For specific applications, it is always advisable to consult the National Electrical Code (NEC) or local regulations to ensure compliance and safety.


What wire size for 15000 Volts and 550 amp service?

There are two distinct questions here. To determine the wire size to carry 15000 volts the circuits load amperage must be stated. The wire size for a 550 amp service is, an 800 MCM copper conductor with an insulation factor of 90 degrees C. This conductor is rated at 555 amps. Parallel 250 MCM will give you a total capacity of 580 amps. A triple run of 2/0 will give you a total capacity of 585 amps.


What size wire is needed for 800 amp service?

Loaded question, what is the voltage, run length, aluminum or copper feeders, expected constant load? Definitely bigger than 4/0


What size of wire needed for 800 ampere 400 volts 500 meters?

For an 800 ampere, 400-volt installation over a distance of 500 meters, the appropriate wire size depends on factors such as allowable voltage drop and the installation method. Typically, for such high current, large conductors like copper or aluminum wires would be required. As a rough estimate, you might need a copper wire size of at least 250 mm² or larger, but it's crucial to consult local electrical codes and standards or a professional engineer for precise calculations and recommendations.


What gauge wire 120 volt 30 amp 800 ft?

For a 120-volt, 30-amp circuit running 800 feet, you would typically need to use a larger gauge wire to compensate for voltage drop. Generally, a 10 AWG copper wire is recommended for this application, but depending on the specific installation conditions and local codes, you might consider using 8 AWG to further reduce voltage drop. Always consult local electrical codes and a qualified electrician to ensure compliance and safety.

Related Questions

What is the amperage rating for 800 mcm?

The amperage rating for 800 MCM (thousand circular mils) of copper wire typically ranges from 380 to 700 amps, depending on factors such as the insulation type, installation conditions, and temperature rating. For aluminum wire, the rating is generally lower, around 300 to 600 amps. It's important to consult the National Electrical Code (NEC) or local regulations for specific applications and conditions. Always consider derating factors for safe and efficient electrical design.


What is the amperage rating of 500 MCM copper conductor?

It depends on a lot of factors. Generally speaking, if the insulation is THHN then the rating is 350 amps. If the insulation is THWN then the rating is 310 amps. The ampere rating for wire depends on the temperature of the environment it will be used in, the insulation rating and the number of circuits installed in a conduit. There are also other factors to consider... like voltage drop in long runs.


How loud is a Storm Cat 800 watt generator?

A Storm Cat 800 watt generator has a decimal rating of between 190 to 265 decibels depending on load and amperage. This is enough noise pollution to cause hearing damage after twenty minutes of exposure.


How many amps is 600 mcm good for?

The ampacity of 600 kcmil (mcm) copper wire varies depending on the application and installation conditions, such as whether it is in conduit or in free air. Generally, 600 kcmil copper wire can carry approximately 700 to 800 amps at a temperature rating of 75°C. For specific applications, it is always advisable to consult the National Electrical Code (NEC) or local regulations to ensure compliance and safety.


What size ground wire should you use on a 1200 amp service?

You need to say whether it's a 150 amp service or a 1200 amp service it has to be one or the other. <<>> A 1/0 copper conductor with an insulation factor of 90 degrees C is rated at 155 amps. There is no ground wire stated for a 150 amp service so the next size up is a 200 amp service. The ground wire for this size is #6 bare AWG. Without knowing what types of loads that are coming off of the distribution a reduced neutral can not be recommended. The neutral will be the same size as the service conductor which is 1/0.


What is State of copper at 800 degrees Celsius?

At 800 degrees Celsius, copper is in solid state. Copper has a melting point of 1085 degrees Celsius, so at 800 degrees Celsius, it remains in its solid form.


What wire size for 15000 Volts and 550 amp service?

There are two distinct questions here. To determine the wire size to carry 15000 volts the circuits load amperage must be stated. The wire size for a 550 amp service is, an 800 MCM copper conductor with an insulation factor of 90 degrees C. This conductor is rated at 555 amps. Parallel 250 MCM will give you a total capacity of 580 amps. A triple run of 2/0 will give you a total capacity of 585 amps.


What size ungrounded conductor for 800 amp service?

A 3/0 copper conductor would allow you up to 100 feet at 800 Amps with only 5 percent voltage drop, assuming 240-volt service. If it were a 3-phase 480-volt service, you could go more than 23 feet with only a 5 percent drop. <<>> The size of conductors for an 800 amp service could be sized in several ways. Using a single conductor is out of the question as the size will be impossible to bend or handle. A 2000MCM wire only has a rating of 775 amps. Most high amperage services will use parallel runs to add up to the required amperage. A parallel run of 600 MCM will give you a total of 910 amps. A triple parallel run of 300 MCM will give you a total of 885 amps. A quad parallel run of 3/0 will give you an amperage of 840 amps. The key here is to find the most economical way of installing the service. Take into account the availability of triple barrel or four barrel lugs, wire costs for the larger sizes and the labour to man handle the larger sizes into the main switch. These size services that I have installed, the customer opted for the four barrel lugs with 3/0 wire. The 3/0 wire is a readily available item even though the lugs may have to be a special order.


What size ground wire for 800 amp service?

For an 800 amp service, typically a 3/0 or 4/0 copper conductor or 250kcmil aluminum conductor would be appropriate for the grounding wire. However, it is recommended to consult with a qualified electrician or the local electrical code for specific requirements based on the installation conditions.


What size wire is needed for 800 amps?

Loaded question, what is the voltage, run length, aluminum or copper feeders, expected constant load? Definitely bigger than 4/0


What state would copper be at 800 degrees?

It would be solid... Copper's melting point is as high as 1,084 C


What size wire is needed for 800 amp service?

Loaded question, what is the voltage, run length, aluminum or copper feeders, expected constant load? Definitely bigger than 4/0