Using a higher amp breaker than recommended can create a safety hazard. It is not recommended to use a 40 amp breaker on a water heater that requires a 30 amp breaker. You should consult with a licensed electrician to properly address the wiring issue.
There are two things to think about here. First of all a 200 amp breaker will not physically fit into a 100 amp panel. This is so designed because the panel buss is not designed to conduct 200 amps before the current is cut off. A 100 amp rating on the panel is the maximum amount of current that the manufacturer states, that can be handled safely. Second if the 200 amp breaker is in the main panel then everything downstream from that breaker has to be rated for 200 amp conductivity. The wire size will have to be 3/0 from the breaker to the first over current device in the sub panel which will be the sub panel's main breaker. The sub panel can not be a load center but will have to be a combination panel. I doubt that the 100 amp sub panel's main breaker lugs would be large enough to connect the 3/0 cable.
== == === === Gauge #6 wires are best for this application. The breaker and wire should fit in your main panel unless it is already overloaded. Get advice from an electrician. ----- See Discussion for additional information As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed. Before you do any work yourself,on electrical circuits, equipment or appliances,always use a test meter to ensure the circuit is, in fact, de-energized.IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOBSAFELY AND COMPETENTLYREFER THIS WORK TO QUALIFIED PROFESSIONALS.
If the wire will fit into the breakers terminal without cutting off any strands from the #8 conductor, then it is OK to use that size. This situation usually happens when a larger size wire has to be used to overcome voltage drop when the load is quite a distance away.
Yes, a 2 pole 60 amp ITE Gould or Westinghouse breaker can replace a 2 pole 60 amp T and B unit as long as they have the same voltage rating and fit properly in the panel. It is important to make sure that the replacement breaker is compatible with your specific panel model.
Using a higher amp breaker than recommended can create a safety hazard. It is not recommended to use a 40 amp breaker on a water heater that requires a 30 amp breaker. You should consult with a licensed electrician to properly address the wiring issue.
Yes, a 30 amp breaker is a 30 amp breaker. It must however be able to fit the box it is installed in.
It will work, but the draw backs are that the larger diameter wire is more expensive and it may not fit the 20 A devices well such as the breaker itself and any branch outlets or switches. It is also harder to run because of its bigger size. The voltage drop will be less across the larger wire, so that is likely the biggest advantage if you have a long run.
You could if it fit properly in the connector, but it would be massive overkill since you only need 12 AWG wire. You also have to make sure the load can physically accommodate that larger size wire. Every so often someone will replace an electric cooktop witha gas one. All of the new gas cooktops require a 110v outlet. The old electric cooktop may have been run with a 50 amp breaker (and probably 6 gauge wire) In order to convert this 220 v circuit to a 110v circuit we change to a 20amp breaker. Depending upon the brand of breaker sometimes the wire will fit into it. If not, we splice on a short piece of 12 gauge wire and then connect to the breaker.
There are two things to think about here. First of all a 200 amp breaker will not physically fit into a 100 amp panel. This is so designed because the panel buss is not designed to conduct 200 amps before the current is cut off. A 100 amp rating on the panel is the maximum amount of current that the manufacturer states, that can be handled safely. Second if the 200 amp breaker is in the main panel then everything downstream from that breaker has to be rated for 200 amp conductivity. The wire size will have to be 3/0 from the breaker to the first over current device in the sub panel which will be the sub panel's main breaker. The sub panel can not be a load center but will have to be a combination panel. I doubt that the 100 amp sub panel's main breaker lugs would be large enough to connect the 3/0 cable.
== == === === Gauge #6 wires are best for this application. The breaker and wire should fit in your main panel unless it is already overloaded. Get advice from an electrician. ----- See Discussion for additional information As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed. Before you do any work yourself,on electrical circuits, equipment or appliances,always use a test meter to ensure the circuit is, in fact, de-energized.IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOBSAFELY AND COMPETENTLYREFER THIS WORK TO QUALIFIED PROFESSIONALS.
If the wire will fit into the breakers terminal without cutting off any strands from the #8 conductor, then it is OK to use that size. This situation usually happens when a larger size wire has to be used to overcome voltage drop when the load is quite a distance away.
It's necessary to look at the dyer to see how much current it uses, which should be on the maker's plate near where the cable enters the appliance. If it uses less than 50 amps, a 50 amp cable is all right.
No, if you have a Square D distribution panel only Square D breakers will fit in it.
Yes, a 2 pole 60 amp ITE Gould or Westinghouse breaker can replace a 2 pole 60 amp T and B unit as long as they have the same voltage rating and fit properly in the panel. It is important to make sure that the replacement breaker is compatible with your specific panel model.
For a 10 amp, 250 volt circuit, you should install a circuit breaker rated for at least 10 amps and 250 volts. A common option would be a single-pole, 10 amp circuit breaker designed for 240-250 volt applications. Be sure to check the specifications and compatibility with your specific electrical panel.
I believe that the wires supplying a 30 amp circuit must be at least 10 gauge. If you have 14 or 12 gauge wires going to or from your 15 amp breaker, then drawing 30 amps over it could cause a fire hazard. It's like using those cheapo non-UL certified extension cords to plug a MILLION X-mas lights into (drawing more power than the wires can handle). You also have to make sure this GFI outlet you refered to is rated for 30 amps. Do not simply swap out breakers. Overloading the wires in the circuit protected by that breaker will cause a fire. If you need a 30 amp circuit you must run #10 gauge wire.